Display units, System units, Settings display modes – Basler Electric BE1-11m User Manual
Page 300

288
9424200996 Rev L
Setting
Range
Increment
Unit
Default
CT Source
*
CT1 or CT2
n/a
n/a
CT1
Phase VT Ratio
1 to 10,000
0.01
turns
ratio
1
Phase VT Connection
AB, BC, CA, AN, BN, CN, 3W-D,
or 4W-Y
n/a
n/a
4W-Y
27/59 Mode
PP or PN
n/a
n/a
PN
27R Mode
PP or PN
n/a
n/a
PN
Aux VT Ratio
1 to 10,000
0.01
turns
ratio
1
Aux VT Connection
AB, BC, CA, AN, BN, CN, or
Ground
n/a
n/a
AN
* For protection systems equipped with two sets of CTs.
Display Units
The Display Units screen is shown in Figure 240.
System Units
This setting configures the BE1-11m to display and report temperature in English or metric units of
measure.
Settings Display Modes
This setting defines how threshold settings are displayed in BESTCOMSPlus. Either primary units or
secondary units can be selected. The default setting is secondary units. The front panel displays
threshold settings in secondary units only.
Figure 240. Display Units Screen
Configuration
BE1-11m