Operational settings, N table 21 – Basler Electric BE1-11m User Manual
Page 77

9424200996 Rev L
65
Table 21. Logic Inputs and Outputs
Name
Logic Function
Purpose
Block
Input
Disables the 50BF function when true
50BFI
Input
Starts the 50BF timer when true
52BFI
Input
Starts the 50BF timer when true
Trip
Output
True after the 50BF Delay Timer expires
ReTrip
Output
True when the 50BF Delay Timer is actively timing
Operational Settings
Breaker failure element operational settings are configured on the Breaker Fail (50BF) settings screen
(Figure 47) in BESTCOMSPlus. Settings ranges and defaults are summarized in Table 22.
Figure 47. Breaker Fail Settings Screen
Table 22. Operational Settings
Setting
Range
Increment Unit of Measure
Default
Mode
Disabled or Enabled
n/a
n/a
Disabled
Source
*
CT Circuit1 or CT Circuit 2
n/a
n/a
CT Circuit 1
Pickup (Phase & Ground)
0 or 0.25 to 10.00 (5A CTs)
0 or 0.05 to 2.00 (1A CTs)
0 or 0.01 to 0.5 (SEF)
varies
amps
0
Control Timer
0 or 50 to 999
varies
milliseconds
50
Delay Timer
0 or 50 to 999
varies
milliseconds
50
* For protection systems equipped with two sets of CTs.
BE1-11m
Breaker Failure (50BF) Protection