Basler Electric BE1-11m User Manual
Page 572

560
9424200996 Rev L
Figure 395. Protection, Voltage, Undervoltage (27P-1) Screen
Undervoltage (27P-2) Starting
The 27P-2 protection element is set to trip when source voltage is too low for a successful start. The
motor manufacturer data indicates that the minimum voltage for a successful start is 85 percent of
nominal. The 27P-2 element is set to prohibit starting when voltage is below 85 percent of nominal. The
pickup setting is calculated in Equation 79.
πππππ’π = 85% β πππππππ ππππ‘πππ β
1
πππ
= 0.85 β 12,000 β
1
100
= 102 π π ππππππππ¦
Equation 79. 27P-2 Pickup
Set a threshold to deactivate the element when there is no motor activity. The inhibit level is calculated in
Equation 80.
πΌπβππππ‘ πΏππ£ππ = 20% β πππππππ ππππ‘πππ β
1
πππ
= 0.20 β 12,000 β
1
100
= 24 π π ππππππππ¦
Equation 80. 27P-2 Inhibit Level
Select Three of Three mode, set the Pickup setting to 102 V, set the Inhibit Level to 24 V, and set the
Time Delay to 0 ms as shown in Figure 396.
Settings Calculation Examples
BE1-11m