Motor Manufacturer Data
Motor manufacturer data should be reviewed before configuring the BE1-11m. Typical motor
manufacturer data is listed below.
●
GENERAL
○
HP .................................................................. 2900
○
Full-Load Amps (FLA) ................................... 363
○
Maximum Locked Rotor Current (LRA) ......... 600%
○
Bus Voltage ................................................... 4 kV
○
Service Factor................................................ 1.0
○
Stator Insulation Class ................................... F (155
°C per NEMA MG-1 Standard)
○
Ambient Temperature Rating ........................ 40
°C
○
Stator Temperature Rise ............................... 80
°C
○
Subtransient Reactance Xd” .......................... 0.15 pu, 2432 kVA base
●
RTDs
○
Six Stator RTDs ............................................. 100
Ω, 3-wire element, platinum
○
Two Bearing RTDs ........................................ 100
Ω, 3-wire element, platinum
○
One Ambient RTD ......................................... 100
Ω, 3-wire element, platinum
●
STARTING
○
Minimum Starting Voltage ............................. 85%
○
Hot Safe Stall Time ........................................ 9 seconds
○
Cold Safe Stall Time ...................................... 10 seconds
○
Rotor WK
2
...................................................... 410 lb-ft
2
●
CONSECUTIVE STARTS
○
Ambient Temperature .................................... 3 starts
■
Idle Starts Time ................................ 45 minutes
■
Running Starts Time ......................... 20 minutes
○
Operating Temperature ................................. 2 starts
■
Idle Starts Time ................................ 45 minutes
■
Running Starts Time ......................... 45 minutes
●
THERMAL TIME CONSTANT
○
Ambient (Stopped Condition) ........................ 75 minutes
○
Operating (Running Condition) ...................... 60 minutes
●
RUNNING
○
Ride Through Minimum Voltage .................... 75% for 60 seconds
○
Bearing Alarm Temperature .......................... 90
°C
○
Bearing Trip Temperature ............................. 95
°C
●
OPERATING PERFORMANCE
○
Load % ........................................................... 100 ...... 75 ........ 50
○
Amps .............................................................. 363 ...... 276 ...... 190
○
Efficiency % ................................................... 95.5 ..... 95.3 ..... 94.7
○
PF .................................................................. 90 ........ 89 ........ 87
●
OTHER
○
Name
○
Location
○
System Frequency
○
System Rotation
Settings Calculation Examples
BE1-11m