N table 17 – Basler Electric BE1-11m User Manual
Page 67

9424200996 Rev L
55
Table 17. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled or 3 Phase
n/a
n/a
Disabled
Source
*
CT Circuit 1 or CT Circuit 2
n/a
n/a
CT Circuit 1
Pickup
0 or 0.5 to 100 (5A CTs)
0 or 0.1 to 20 (1A CTs)
varies
amps
0
Inhibit Level
0 or 0.5 to 100 (5A CTs)
0 or 0.1 to 20 (1A CTs)
varies
amps
0
Time Delay
0 to 60,000
varies
milliseconds
0
* For protection systems equipped with two sets of CTs.
BE1-11m
Instantaneous Undercurrent (37) Protection