Ul recognition, Csa certification, Gost-r certification – Basler Electric BE1-11m User Manual
Page 460: Halt (highly accelerated life testing), Dnp certification

448
9424200996 Rev L
•
EN 50178 – Electronic Equipment for use in Power Installations
•
EN 61000-6-2 – Electromagnetic Compatibility (EMC), Generic Standards, Immunity for Industrial
Environments
•
EN 61000-6-4 – Electromagnetic Compatibility (EMC), Generic Standards, Emission Standard for
Industrial Environments
UL Recognition
This product is recognized to applicable U.S. and Canadian safety standards and requirements by UL.
Standard used for evaluation:
•
UL 508
UL Recognition for Style xxxxxxxxxxxCxx
This product is recognized to applicable U.S. and Canadian safety standards and requirements by UL.
Evaluation to Class 1, Div 2, Groups A, B, C, and D, Temperature Code T4 for Hazardous Location
Service. Suitable for use in Class 1, Division 2, Groups A, B, C, and D hazardous locations only.
Standards used for evaluation:
•
UL 508
•
ISA 12.12.01
•
CSA C22.2 No. 213-M1987
Warning! - EXPLOSION HAZARD
Do not disconnect equipment unless power has been switched off or
the area is known to be non-hazardous.
Substitution of components may impair suitability for Class 1,
Division 2.
Do not engage USB unless power has been switched off or the area is
known to be non-hazardous.
CSA Certification
This product was tested and has met the certification requirements for industrial control equipment.
Standards used for evaluation:
•
CSA C22.2 No. 14
GOST-R Certification
GOST-R certified per the relevant standards of Gosstandart of Russia.
HALT (Highly Accelerated Life Testing)
Basler Electric uses HALT to prove that our products will provide the user with many years of reliable
service. HALT subjects the device to extremes in temperature, shock, and vibration to simulate years of
operation, but in a much shorter period span. HALT allows Basler Electric to evaluate all possible design
elements that will add to the life of this device. As an example of some of the extreme testing conditions,
the BE1-11m was subjected to temperature extremes of –80
°C to +130°C,
vibration extremes of 5 to 45 G
at +20
°C, and temperature/vibration extremes of 45 G over a temperature range of –60°C to +110°C.
Combined temperature and vibration testing at these extremes proves that the BE1-11m is expected to
provide long-term operation in a rugged environment. Note that the vibration and temperature extremes
listed in this paragraph are specific to HALT and do not reflect recommended operation levels. These
operational ratings are listed under Temperature.
DNP Certification
DNP3-2009, V2.6 compliant, Subset Level 2, by Advanced Control Systems, Inc.
Specifications
BE1-11m