Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure
Figure 271. BESTlogicPlus Settings
Step 3: Prepare to monitor 66 function operation. Operation can be verified by monitoring OUT1
(Starting), OUT2 (Stopped), OUT3 (Start Blocked), and OUT4 (Start Blocked Removed). See
Figure 271. The test sequence is illustrated in Figure 272.
Figure 272. Test Sequence
Step 4: Connect a three-phase current source to terminals D1 and D2 (IA), D3 and D4 (IB), and D5 and
D6 (IC).
Step 5: Apply 10 Aac three-phase current for approximately one minute (simulate motor starting). Note
that this is the first start. Verify that OUT1 (Starting) closes and OUT2 (Stopped) opens. Start
the timer when OUT1 (Starting) closes. The timer will be stopped when OUT4 (Start Blocked
Removed) closes in step 9. The expected timing is 360 seconds.
Step 6: Remove three-phase current for approximately one minute. Verify that OUT1 (Starting) opens
and OUT2 (Stopped) closes.
OUT1 (Starting)
OUT2 (Stopped)
OUT3 (Start Blocked)
OUT4 (Stop Timer)
First
Start
Second
Start
Start
Unblocked
Current
Applied
Current
Applied
Current
Removed
Current
Removed
6 Minutes
Time Interval Setting
P0061-55
Approx.
1 minute
Approx.
1 minute
Approx.
1 minute
Approx.
3 minutes
Starts per Time Interval (66) Test
BE1-11m