Motor manufacturer data, Kv bus, Be1-11 m – Basler Electric BE1-11m User Manual
Page 550

538
9424200996 Rev L
Figure 367. Single-Line Drawing, Phase Differential Protection (5,000 HP Synchronous Motor Example)
Motor Manufacturer Data
Motor manufacturer data should be reviewed before configuring the BE1-11m. Typical motor
manufacturer data is listed below.
●
GENERAL
○
HP .....................................................................5000 HP
○
System Frequency ............................................60 Hz
○
Motor Rotation ..................................................1200 RPM
○
Bus Voltage ......................................................12 kV
○
Full-Load Amps (FLA, Synchronous) ...............205 A
○
Full-Voltage No-Load Stator Current in Sync ...128 A (no excitation)
○
Full-Voltage Line Current (95% Speed) ...........392 A (no excitation)
○
Maximum Locked Rotor Current (Max. LRA) ...755 A
○
Service Factor...................................................1.15
○
Power Factor Minimum .....................................0.90
○
Stator Insulation Class ......................................F (155
°C per NEMA MG-1 Standard)
○
Ambient Temperature Rating ...........................40
°C
○
Stator Temperature Rise ..................................76
°C
○
Subtransient Reactance Xd” .............................0.368 pu, 4263 kVA base
○
Hot Safe Stall Time ...........................................8.5 seconds
○
Cold Safe Stall Time .........................................10.7 seconds
12-kV Bus
52
M
2 or 3 PTs
R
T
D
3 CTs
3 CTs
P
0
0
6
9
-6
5
BE1-11m
Settings Calculation Examples
BE1-11m