Restart inhibit protection, Automatic setting group characteristics, Bestlogic™plus – Basler Electric BE1-11m User Manual
Page 470

458
9424200996 Rev L
Restraint Slope 1
Setting Range ........................................................... 5 to 100%
Restraint Slope 2
Setting Range ........................................................... 15 to 140%
Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy....................................................................
±1% or ±1 cycle, whichever is greater, plus trip time
for instantaneous response (0.0 setting)
*
* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents ≥ 5 times the pickup
setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.
Restart Inhibit Protection
Restart Delay
Setting Range ........................................................... 0 to 7,200 min
Accuracy....................................................................
±1.5% or ±3 cycles
Time Between Starts
Setting Range ........................................................... 0 to 7,200 min
Accuracy....................................................................
±1.5% or ±3 cycles
Automatic Setting Group Characteristics
Number of Setting Groups ........................................ 4
Control Modes
Automatic .................................................................. Cold-Load Pickup, Dynamic Load or Unbalance
External ..................................................................... Discrete Input Logic, Binary Input Logic
Switch Threshold
Range ........................................................................ 0.1 to 25 A (5 A), 0.02 to 5 A (1 A)
Accuracy....................................................................
±2% or ±0.05 A (5 A), ±2% or ±0.01 A (1 A)
Switch Time
Range ........................................................................ 0 to 60 min with 1 min increments where 0 =
disabled
Accuracy....................................................................
±0.5% or ±2 s, whichever is greater
BESTlogic
™Plus
Update Rate .............................................................. ¼ cycle
Specifications - 25 Hz Operation
BE1-11m