One-shot/retriggerable mode – Basler Electric BE1-11m User Manual
Page 430

418
9424200996 Rev L
despite a second 43-1 OFF to ON initiate signal while the duration timer was active. Figure 279
illustrates the timing relationship of the 43-1 switch and 62-1 timer.
Figure 279. One-Shot/Non-Retriggerable Mode
Step 6: (Optional.) Repeat steps 1 through 5 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, and 62-8.
Step 7: (Optional.) Repeat steps 1 through 6 for settings group 1, 2, and 3.
One-Shot/Retriggerable Mode
Step 1: Use BESTCOMSPlus to send the operational settings in Table 184 to the BE1-11m. Retain the
logic settings from Figure 276.
Table 184. Operational Settings (One-Shot/Retriggerable Mode)
Setting
Value
BESTCOMSPlus Screen
Description
62-1 Mode
One-
Shot/Retriggerable
Control, Logic Timers (62)
Sets 62-1 to One-
Shot/Retriggerable mode
62-1 Time
Delay 1 (T1)
15,000 ms
Control, Logic Timers (62)
Sets 62-1 pickup time delay to
15,000 ms
62-1 Time
Delay 2 (T2)
20,000 ms
Control, Logic Timers (62)
Sets 62-1 dropout time delay
to 20,000 ms
43-1 Mode
Pulse
Control, Virtual Control
Switches (43)
Sets 43-1 to Pulse mode
62-1 Target
Enabled
Target Configuration,
Targets screen.
Enables 62-1 target
Step 2: Step 4 supplies the 62-1 timer with a momentary initiate input by pulsing the 43-1 switch from
an OFF state to an ON state and then back to an OFF state. You can view the state changes of
the 43-1 switch at the Metering > Control > Virtual Switches screen on the front-panel display.
Step 3: Close communication with BESTCOMSPlus.
Step 4: Using the front-panel display, navigate to the Metering > Control > Virtual Switches screen.
Highlight the first switch (43-1) and press the Right key on the front panel to enter the 43-1
control screen. Use the Edit key to login. Highlight Operate and then press the Edit key to
change the state of the 43-1. Using the Up/Down keys select PUL and then press the Edit key.
Step 5: Repeat step 4.
Step 6: Wait at least 15 seconds (but no longer than 35 seconds) and then repeat step 4.
P
0
0
3
5
-3
1
0
2
-2
7
-0
6
Block
Initiate
62-x
Logic Timers (62) Test
BE1-11m