Incomplete sequence (48) protection, Element operation, Trip – Basler Electric BE1-11m User Manual
Page 115: Element blocking, Logic connections

9424200996 Rev L
103
Incomplete Sequence (48) Protection
The incomplete sequence (48) element announces an incomplete sequence if the motor starts but does
not reach the running state before the time interval expires.
Element operational settings are configured on the Restart Inhibit settings screen in BESTCOMSPlus
®. A
summary of the logic inputs and outputs and operational settings appears at the end of this chapter.
BESTCOMSPlus Navigation Path: Settings Explorer, Protection, Motor, Incomplete Sequence (48)
HMI Navigation Path: Settings Explorer, Protection, Settings Group x (where x = 0 to 3), Motor
Protection, Incomplete Sequence 48
Element Operation
Trip
Assertion of the Starting output of the Motor Status logic element initiates a timer that begins timing to a
trip. The duration of the timer is established by the Time Interval setting. A Time Interval of zero (0) makes
the 48 element instantaneous with no intentional time delay. In BESTlogic
™Plus, the Starting output can
be connected to other logic elements to annunciate the condition or control other elements in logic.
The Trip output becomes true if the time interval expires before the Running output of the Motor Status
logic element becomes true. In BESTlogicPlus, the Trip output can be connected to other logic elements
and to a physical relay output to annunciate the condition and to initiate corrective action. If a target is
enabled for the element, the BE1-11m will record a target when the Trip output becomes true. See the
chapter for more information about target reporting.
If the Running output of the Motor Status logic element becomes true before the element time interval
expires, the timer is reset, no corrective action is taken, and the element is rearmed for any other
incomplete sequence occurrences.
Refer to the
chapter for more information on the Motor Status logic element.
Element Blocking
The Block input provides logic-supervision control of the element. When true, the Block input disables the
element by forcing the Trip output to logic 0 and resetting the element timer. Connect the element Block
input to the desired logic in BESTlogicPlus. When the element is initially selected from the Elements view,
the default condition of the Block input is a logic 0.
Logic Connections
Incomplete sequence element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The incomplete sequence element logic block is illustrated in Figure 71. Logic inputs
and outputs are summarized in Table 40.
Figure 71. Incomplete Sequence Element Logic Block
BE1-11m
Incomplete Sequence (48) Protection