Logic connections, Operational settings – Basler Electric BE1-11m User Manual
Page 59

9424200996 Rev L
47
element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the
Elements view, the default condition of the Block input is a logic 0.
Logic Connections
Auxiliary overvoltage element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The auxiliary overvoltage element logic block is illustrated in Figure 36. Logic inputs
and outputs are summarized in Table 12.
Figure 36. Auxiliary Overvoltage Element Logic Block
Table 12. Logic Inputs and Outputs
Name
Logic Function
Purpose
Block
Input
Disables the 59X function when true
Trip
Output
True when the 59X element is in a trip condition
Pickup
Output
True when the 59X element is in a pickup condition
Operational Settings
Auxiliary overvoltage element operational settings are configured on the Overvoltage (59X) settings
screen (Figure 37) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 13.
Figure 37. Auxiliary Overvoltage Settings Screen
BE1-11t
Auxiliary Overvoltage (59X) Protection