Thermal curve (49tc), Standard curve – Basler Electric BE1-11m User Manual
Page 503

9424200996 Rev L
491
Thermal Curve (49TC)
The Standard and IEC curves are defined below.
Standard Curve
The Standard Curve Time Dial setting determines the time to trip when the 49TC element is configured
for Standard Curve mode. The standard curve provides a
I
eq
2
curve with a range of time dial settings that
accommodate a wide range of motor timings. The standard curve equation is shown in Equation 35.
t = TD × 88.744132 × ln
⎣
⎢
⎢
⎢
⎡ �
I
eq
S ∙ SF ∙ FLA�
2
�
I
eq
S ∙ SF ∙ FLA�
2
− 1⎦⎥
⎥
⎥
⎤
With max value of
I
eq
/(S
•SF•FLA) of 10.
Equation 35. Standard Curve
Where:
t
= Operating time
I
eq
= Measured equivalent motor current
TD = Time Dial
FLA = Full Load Amps
SF = Service Factor
S
= Overload Scaler
ln
= Natural log
BE1-11m
Time Curve Characteristics