Basler Electric BE1-11m User Manual
Page 563

9424200996 Rev L
551
πππππ’π = 1.7 π·πΆ ππππ ππ‘ β (125% ππ πΏπ π΄ + 2% πππππ’π πππππππππ) β πππ₯ πΏπππππ π ππ‘ππ πΆπ’πππππ‘ β
1
πΆππ
= 1.7 β (1.25 + 0.02) β 755 π΄ β
1
60 = 27.17 π΄ π ππππππππ¦
Equation 63. 50-1 Pickup
Set for three-phase mode so that any phase exceeding the setting will pick up the element. Set the
Pickup setting to 27.17 A. Typically, CT circuit 1 is used because it is on the feed side of the motor. See
Figure 383.
Figure 383. Protection, Current, Instantaneous Overcurrent (50-1) Screen
Instantaneous Overcurrent (50-2) - Ground Fault Protection
The system is solidly grounded so that a ground fault draws current in the magnitude of a three-phase
fault per IEEE C37.96-2000, IEEE Guide for AC Motor Protection. To determine the three-phase fault
current, consider that the motor subtransient reactance of 0.368 is the limiting impedance. The pickup
setting is calculated using Equation 64. A pickup setting of 1/3 of the instantaneous three-phase fault
current is recommended per IEEE C37.96-2000, IEEE Guide for AC Motor Protection. During starting, CT
saturation can produce false residual currents, so we use the running mode current FLA. The circuit CT
ratio (CTR) is 60.
πππππ’π = οΏ½
1
π"π
β
πΉπΏπ΄
πΆπ π ππ‘πποΏ½ β
1
3 = οΏ½
1
0.368 β
205
60 οΏ½ β
1
3 = 3.09 π΄ π ππππππππ¦
Equation 64. 50-2 Pickup
Select 3I0 (residual) mode and set the Pickup setting to 3.09 A as shown in Figure 384.
Figure 384. Protection, Current, Instantaneous Overcurrent (50-2) Screen
BE1-11m
Settings Calculation Examples