Page 557

9424200996 Rev L
545
Figure 375. Programmable Inputs, Remote RTD, RTD Type Selection Screen
RTD Block Configuration
For this example, the RTDs are configured into three configuration blocks. Six of the RTDs are used for
stator thermal measurements, two are used for bearing measurements, and one is used for ambient
temperature.
Navigate to Programmable Inputs, Remote RTD, RTD Block Configuration and set RTD Configuration
Blocks 1-3 as shown in Figure 376.
Figure 376. Programmable Inputs, Remote RTD, RTD Block Configuration Screen
BE1-11m
Settings Calculation Examples