Operational settings, Table 40 – Basler Electric BE1-11m User Manual
Page 116

104
9424200996 Rev L
Table 40. Logic Inputs and Outputs
Name
Function
Purpose
Block
Input
Disables the 48 function when true
Trip
Output
True when the 48 element is in trip condition
Operational Settings
Incomplete sequence operational settings are configured on the Incomplete Sequence (48) settings
screen (Figure 72) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 41.
Figure 72. Incomplete Sequence Settings Screen
Table 41. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled or Enabled
n/a
n/a
Disabled
Time Interval
0 to 7,200
0.01
seconds
0
Incomplete Sequence (48) Protection
BE1-11m