Functional test report, Pickup verification (phase mode) – Basler Electric BE1-11m User Manual
Page 376

364
9424200996 Rev L
Table 161. Timing Test Settings (IG Mode)
Sensing
Type
Time
Dial
Applied
Current
5 A
0.5
1.00 A
2.50 A
12.50 A
5.0
1.00 A
2.50 A
12.50 A
9.9
1.00 A
2.50 A
12.50 A
1 A
0.5
0.20 A
0.50 A
2.50 A
5.0
0.20 A
0.50 A
2.50 A
9.9
0.20 A
0.50 A
2.50 A
SEF
0.5
0.20 A
0.50 A
0.80 A
5.0
0.20 A
0.50 A
0.80 A
9.9
0.20 A
0.50 A
0.80 A
Functional Test Report
Pickup Verification (Phase Mode)
Pickup Setting Range = 0.5 to 16 A for 5A sensing
0.1 to 3.2 A for 1A sensing
Pickup Accuracy =
±2% or ±50 mA, whichever is greater for 5A sensing
±2% or ±10 mA, whichever is greater for 1A sensing
Inverse Overcurrent (51) Test