General settings – Basler Electric BE1-11m User Manual
Page 530

518
9424200996 Rev L
General Settings
Display Units
Settings in this example are in metric and secondary units, based upon multiples of FLA (Full Load Amps)
and phase-to-phase voltages, unless otherwise specified. Phase-to-phase voltages are configured during
phase VT setup.
Use the Settings Explorer in BESTCOMSPlus
® to navigate to the General Settings, Display Units screen.
Select Metric for System Units and Secondary Units for Settings Display Modes, Thresholds. Refer to
Figure 340.
Figure 340. General Settings, Display Units Screen
Style Number
The BE1-11m style number shown in Figure 341 is used in this application example. The style number is
defined below.
Figure 341. BE1-11 Style Number
M ......... Application Option ...................... Motor
6 .......... Phase CT Option ........................ CT1 - 5 Amp Nominal / CT2 - 5 Amp Nominal
D .......... Ground CT Option ...................... CT1 - 5 Amp Nominal / CT2 - 5 Amp Nominal
1 .......... Power Supply Option ................. 48/125 Vac/dc
M ......... RS-485 Port Protocol ................. Modbus
™
1 .......... Ethernet Protocol ....................... BESTnet
™Plus Only
J .......... Case Option ............................... Vertical Case
2 .......... Alarm Contact Option ................. Normally Closed (closes upon power removal / watchdog failure)
P .......... Option 1 ...................................... Phase Differential
0 .......... Network Connections ................. Copper
E .......... Language ................................... English
0 .......... Option 2 ...................................... None
00 ........ Firmware Option ......................... Latest Release
Settings Calculation Examples
BE1-11m