beautypg.com

3 connecting the cables to the pem, System installation – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual

Page 82

background image

System Installation

AXP 1410 Installation and Use (6806800H70L)

82

Terminating this lug is identical to terminating standard lugs. To minimize shorting of the
terminals, the lugs must be insulated according to the following illustration.

3.3.2.3

Connecting the Cables to the PEM

In a redundant configuration, each PEM must be connected to a separate DC power source.
Power is introduced to each PEM’s terminal block on the front of the module (power input
cable and return cable). The lugs provide secure contact for the cable and prevent the power
cables from rotating. A plastic housing covers the power feeds and returns and is attached with
one screw. Refer to

Figure 3-2

for detail.

Heat shrink should be placed as close to the hole as possible (0.15") apart. The heat shrink
tube should be cut approximately at a 30° angle.

To cable a dual breaker DC system, read all cautions and warnings, properly ground the
equipment by following the procedure in

Grounding the System

on page 84

, and follow these

steps. This procedure assumes that the PEMs are preinstalled in the shelf.

This manual is related to the following products: