beautypg.com

1 voltage sensors, Table 7-37, Sensor no. 2 +3.3v – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual

Page 176: Fru information and sensor data records

background image

FRU Information and Sensor Data Records

AXP 1410 Installation and Use (6806800H70L)

176

7.3.5.1

Voltage Sensors

The following sensors measure voltages of the PEM.

Table 7-37 Sensor No. 2 +3.3V

Feature

Raw Value/Description

Interpreted Value

Sensor Name

+3.3V

Device

Sensor Type

0x02

Voltage

Class

0x01

Threshold

Sensor Owner LUN

0x00

Entity ID

0x0A

Power Supply

Entity Instance

0x60

Rearm mode

Auto

Hysteresis support

Readable/Settable

Threshold access support

Readable/Settable

Event message control

Entire Sensor only

Readable threshold mask,
Settable threshold mask (bytes
19, 20)

0x3F, 0x3F

Upper and Lower Non-Critical, Critical
and Non-Recoverable Thresholds are
Readable and Settable

Reading Type

Unsigned

Lower Non-Critical, Critical and
Non-Recoverable thresholds

0xD8, 0xD4, 0xD1

(3.1104, 3.0528, 3.0096) Volts

Upper Non-Critical, Critical and
Non-Recoverable thresholds

0xF4, 0xF7, 0xFA

(3.5136, 3.5568, 3.6) Volts