2 ipmb link sensor, Table 7-47, Sensor no. 1, ipmb physical – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual
Page 184: Ipmb link sensor, Fru information and sensor data records

FRU Information and Sensor Data Records
AXP 1410 Installation and Use (6806800H70L)
184
7.3.6.2
IPMB Link Sensor
The following table describes the IPMB link sensor on the PEMs.
Hysteresis support
Threshold access support
Event Message Control
Entire Sensor Only
Readable threshold mask,
Settable threshold mask (bytes
19, 20)
Reading Type
According to PICMG 3.0
Lower Non-Critical, Critical and
Non-Recoverable thresholds
0x84, 0x77, 0x71
(42.24, 38.08, 36.16) Volts
Upper Non-Critical, Critical and
Non-Recoverable thresholds
0xE1, 0xEB, 0xEE
(72, 75.20, 76.16) Volts
Table 7-46 Sensor No. 0, Hot Swap (continued)
Feature
Raw Value/Description
Interpreted Value
Table 7-47 Sensor No. 1, IPMB Physical
Feature
Raw Value/Description
Interpreted Value
Sensor Name
IPMB Physical
Type of Measurement
IPMB Link State
Class
0x6F
Discrete
Event/Reading Type
0x6F
Sensor-specific
Sensor Type
0xF1
IPMB Link
Sensor Owner LUN
0x00
Entity ID
0x0A
Entity Instance
0x60
Rearm Mode
Auto
Hysteresis support