5.7.1

Cold Standby

In AXP 1410 systems the shelf managers work in redundancy mode, this means that the HPI
daemon runs on the active shelf manager and is started on the former stand-by shelf manager
once it has become the active one.

When a former standby shelf manager becomes active the following steps are carried out:

Removal of the ShMC IPMI address from the former active shelf manager

Assignment of the ShMC IPMI address to the local IPMC

Assignment of the active virtual IP address

Sending a gratuitous address resolution protocol (ARP)
(broadcast to update arp caches)

Starting the HPI daemon which performs HPI resource discovery for all resources of the
AdvancedTCA shelf

Storing of the resource IDs which were assigned to the former active shelf manager. Thus,
it is possible to reassign these IDs when the session is reestablished.

Closing of all open HPI sessions on the client's side. They have to be reestablished. Any
blocking HPI calls have to be avoided (for example, saHpiGetEvent) and calls with timeouts
have to be used instead.

5.7.1.1

Heartbeat

The shelf managers use two private interfaces to heartbeat each other. The heartbeat interval
is configured to 400 ms and the partner is considered inactive when no responses are received
after five retries within 2 seconds.