Safety Notes
24
Before you begin to set up and cable your new system, consider these guidelines:
Restricted access area: Install the system only in a restricted access area.
Installation codes: This unit must be installed in accordance with the National Electrical
Code, Articles 11016, 11017, and 11018 and the Canadian Electrical Code, Section 12.a
Overcurrent protection: A readily accessible listed branch circuit overcurrent protective
device must be incorporated into the building wiring. For appropriate AWG rating of the
overcurrent protection device see NEC Table 31016 and other national regulations.
The protective bonding conductor depends on your power distribution topology. Make
sure that you use an appropriate protective bonding conductor regarding the rating of the
branch circuit protection.
Install the system safely. Make sure that cables and cords are out of the way.
Make sure that the set-up is comfortable for users.
System
Damage
WARNING: The intra-building port(s) of the equipment or subassembly is suitable for
connection to intra-building or unexposed wiring or cabling only. The intra-building port(s) of
the equipment or subassembly MUST NOT be metallically connected to interfaces that
connect to the OSP or its wiring. These interfaces are designed for use as intra-building
interfaces only (Type 2 or Type 4 ports as described in GR-1089) and require isolation from the
exposed OSP cabling. The addition of Primary Protectors is not sufficient protection in order to
connect these interfaces metallically to OSP wiring.
System
Damage
Environmental contamination can impair system operation. Locate the system in a stable area
free of excess movement and jarring and free of dust, smoke, and electrostatic discharge
(ESD).
Make sure that the temperature does not exceed the operating temperature given in the
environmental requirements in this manual and allow room for proper air flow for cooling.