AXP 1410 Installation and Use (6806800H70L)

Safety Notes

28

Grounding

Electric

Shock

Power Cable
To minimize shock hazard, the system chassis and enclosure must be connected to an
electrical ground. Failure to observe proper grounding practices may cause a variety of noise,
electrostatic discharge, and radio frequency interference problems.

Damage of Circuits
Electrostatic discharge and incorrect product installation and removal can damage circuits or
shorten their life.
Before touching the product or electronic components, make sure that you are working in an
ESD-safe environment.

Serious Injury or Death
This product operates with dangerous voltages that can cause injury or death.
To prevent serious injury or death from dangerous voltages use extreme caution when
handling, testing, and adjusting this equipment and its components.

The following paragraphs are not translated to German because they are only part of the
UL/CSA 60950-1 (section 3.2.1, Annex NAA) standard, not of the European version EN60950-
1. Hiltrud, August, 6th, 2008

This equipment is designed to permit the connection of the earthed conductor of the DC
supply circuit to the earthing conductor at the equipment. If this connection is made, all of the
following conditions must be met:

This equipment shall be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC
supply system earthing electrode conductor is connected.

This equipment shall be located in the same immediate area (such as, adjacent cabinets)
as any other equipment that has a connection between the earthed conductor of the same
DC supply circuit and the earthing conductor, and also the point of earthing of the DC
system. The DC system shall not be earthed elsewhere.