Configuring and Operating the System

AXP 1410 Installation and Use (6806800H70L)

127

5.6.2

Cooling Budget

The shelf cooling is designed to operate with the following temperature rises across the shelf.
This allows cards with these dissipations to operate with commercial grade components, 70C
ambient temperature typical.

The following guidelines can assist in determining the cause of the cooling failure. Also refer to

Environmental Requirements

on page 65

for important information regarding ambient

temperature requirements during servicing. If a cooling failure occurs, the failure may be
caused by a failed fan or possibly a clogged filter. Check the filter first before replacing the FTM.

For further information of nonrecoverable temperature events, refer to

Chapter 7, FRU

Information and Sensor Data Records, on page 145

.

5.6.3

IPMC Circuitry

Preprogrammed FRU and SDR information reside on the FTMs and is accessible from the SAM
via the I

2

C bus. FRU information can be found in the

Chapter 7, FRU Information and Sensor Data

Records, on page 145

.

5.7

Redundancy

The following sections outline the interaction between redundant shelf managers and
redundant hub blades. This interaction is not described within the AdvancedTCA Specification
PICMG 3.0
. The following sections also describe redundancy scenarios with redundant shelf
managers and system managers.

Table 5-8 Cooling Budget

Ambient Temperature

Temperature Rise

25C

Delta T = 20 C

40C

Delta T = 15 C

55C

Delta T = 10 C