Table 7-20, Sensor no. 17 fan 4 outlet, Fru information and sensor data records – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual
Page 161

FRU Information and Sensor Data Records
AXP 1410 Installation and Use (6806800H70L)
161
Readable threshold mask,
Settable threshold mask (bytes
19, 20)
0x3F3F
Upper and Lower Non-Critical, Critical
and Non-Recoverable Thresholds are
Readable and Settable
Reading Type
Unsigned
Lower Non-Critical, Critical and
Non-Recoverable thresholds
0x24, 0x24, 0x24
(902, 902, 902) RPM
Upper Non-Critical, Critical and
Non-Recoverable thresholds
0xCE, 0xE6, 0xF2
(5588, 5610, 5610) RPM
Table 7-20 Sensor No. 17 Fan 4 Outlet
Feature
Raw Value/Description
Interpreted Value
Sensor Name
Fan 4 Outlet
Device
Sensor Type
0x04
Fan
Class
0x01
Threshold
Sensor Owner LUN
0x00
Entity ID
0x1D
Cooling Unit
Entity Instance
0x63
Rearm mode
Auto
Hysteresis support
Readable/Settable
Threshold access support
Readable/Settable
Event message control
Entire Sensor only
Readable threshold mask,
Settable threshold mask (bytes
19, 20)
0x3F3F
Upper and Lower Non-Critical, Critical
and Non-Recoverable Thresholds are
Readable and Settable
Reading Type
Unsigned
Lower Non-Critical, Critical and
Non-Recoverable thresholds
0x24, 0x24, 0x24
(902, 902, 902) RPM
Upper Non-Critical, Critical and
Non-Recoverable thresholds
0xCE, 0xE6, 0xF2
(5588, 5610, 5610) RPM
Table 7-19 Sensor No. 16 Fan 3 Outlet (continued)
Feature
Raw Value/Description
Interpreted Value