System Installation

AXP 1410 Installation and Use (6806800H70L)

81

3.3.2.2

Power Cable Termination

Custom lugs are used with large gauge wires for up to 80 AMPs DC (4 AWG) when connecting
to the PEM. These are shipped with the product.The lugs are angled to allow the cables to be
dressed below the cable management tray, thus protecting the circuit breakers from
accidental tripping.

Figure 3-2

DC Power Connection Detail

OFF

ON

OFF

ON

-48 VDC RTN

-48 VDC

VDC RTN

-48 VDC