4 installing fan tray modules – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual

Page 102

background image

FRU Installation

AXP 1410 Installation and Use (6806800H70L)

102

4.4

Installing Fan Tray Modules

To prevent system damage, the operator must replace the fans within the recommended
service interval shown in the following table to prevent a decline in shelf operability. Make sure
the replacement FTM is available for exchange and ready to install.

When a fan is taken out of operation, the system manager will compensate for the loss by
increasing the speed of the remaining fans. Please read the following caution before replacing
any of the FTMs.

Service Interval for 1 FTM

Temperature Range

Not recommended

40-55°C

Four hours

40°C maximum

Fans may continue to rotate after power is removed. Be careful to keep fingers away from
the bottom of the FTM enclosure.