Configuring and Operating the System
AXP 1410 Installation and Use (6806800H70L)
135
4. If necessary, moves its own active virtual IP address to another interface
5. Reestablishes the HPI session to the active shelf manager with saHpiSessionOpen
6. Waits in saHpiResourcesDiscover until the active shelf manager discovers all
resources
5.7.3.2
Shelf Manager Takeover
Takeover is a process to switch the active and the standby roles of the shelf manager boards.
The system manager initiates and controls this process on the standby shelf manager.
The system manager performs the following steps:
1. Initiates a takeover on the standby shelf manager by running the script: sv_activate
2. Closes the HPI session
3. Moves its own active virtual IP address to the other interface
4. Reestablishes the HPI session to the active shelf manager with saHpiSessionOpen
5. Waits in saHpiResourcesDiscover until the active shelf manager will discover all
resources
5.7.3.3
Shelf Manager Failover
Failover is a process when the standby shelf manager becomes the active one because the
active shelf manager fails.
The reasons for the shelf manager failover can be:
Communication failure between the two shelf managers
Unexpected removal of the active shelf manager
Software failure of the active shelf manager
Failure of the switch through which the virtual IP address is routed
The system manager detects a failover because of timeouts of the HPI calls. The system
manager actions depend on network topology.