Observe the following general safety notes when installing your system:
Restricted access area - The system is only to be installed in a restricted access area.
Installation codes - This unit must be installed in accordance with the National Electrical
Code, Articles 110.16, 110.17, and 110.18 and the Canadian Electrical Code, Section 12.
Conductor ampacity - According to UL 60950, Annex NAE (NEC Article 645-5(a)), the
branch-circuit conductors supply must have an ampacity of not less than 125% of the
total connected load. Per NEC Article 310.15 and Table 310.16, the minimum American
Wire Gauge (AWG) has to be selected.
Overcurrent protection - A readily accessible listed branch-circuit overcurrent protective
device must be incorporated into the building wiring.
Artesyn Embedded Technologies is not responsible for regulatory compliance or malfunction
of any user-modified product.
System Damage
Environmental contamination can impair system operation.
Locate the system in a stable area free of movement and free of dust, smoke, and
electrostatic discharge (ESD). Make sure, that the temperature does not exceed the
operating temperature given in the environmental requirements in this manual and allow
room for proper air cooling.
System Overheating
Improper cooling leads to blade damage.
To ensure proper cooling always operate the system in a horizontal position. Furthermore,
keep clear at least 6 cm adjacent to the cooling vents on the chassis front and back side.