Site Preparation

AXP 1410 Installation and Use (6806800H70L)

66

Shock

Half-sine, 11 ms, 30 m/s

2

Blade level packaging
Half-sine, 6 ms at 180 m/s

2

Vibration
(tested in
target
platform)

0.1g from 5 Hz to 100 Hz and back to 5 Hz
at a rate of 0.1 octave/minute

5-20 Hz at 0.01 g

2

/Hz

20-200 Hz at -3.0 dB/octave
Random 5-20 Hz at 1m

2

/s

3

Random 20-200 Hz at -3 dB/octave

Free fall

-

300mm (11.8 in) (packaged)
25mm (1 in) (unpackaged) per GR-63-
CORE
fully populated system

Noise

ETSI ETS 300 753 (October 1997)
Telecommunication equipment rooms
(attended): 7.2 bel
Measurement of "declared A-weight sound
power level"
All values are applicable to normal
operating conditions (~23°C).

NEBS GR-63-CORE, Issue 3
Telecommunication equipment rooms
(attended): 78 dB
Measurement of "declared A-weight sound
power level"
All values are applicable to normal
operating conditions (~27°C).

-

Table 2-1 Environmental Conditions (continued)

Feature

Operating

Non-Operating (packed state)

The ambient temperature around the shelf and the air inlet temperature must not exceed
55°C (131°F).

The AXP 1410 system regulates the fan speed based on the temperature sensors present
in the system. The fan speed is adjusted to the lowest speed which still keeps the
evaluated temperature readings below or at their respective "upper non-critical
threshold". Hence, the fan speed depends on the ambient temperature, blade design,
temperature threshold settings, and system configuration.