Figure 3-1, Rack mounting dimensions, System installation – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual
Page 78: Installation in a 23’’ eia rack/cabinet

System Installation
AXP 1410 Installation and Use (6806800H70L)
78
You have to keep the following conditions when installing the system into an at least 600 mm
(23.62 inch) deep rack. The physical dimensions in the figure below are in millimeters. Please
ensure that 60% of the rack's rear is open.
Installation in a 23’’ EIA Rack/Cabinet
Front mounting brackets are required to attach the shelf to an EIA 23" frame.
1. Locate the standard mounting hole and slot locations on the front mounting
flanges on the AXP 1410 shelf.
2. Fasten the mounting brackets to the back side of the front chassis flanges using M6
screws x 12mm at each of the 5 locations.
3. Be sure to mount the shelf with metal screws or bolts that give a good electrical
connection between the screws or bolts and the mounting surface.
Figure 3-1
Rack Mounting Dimensions
13U Shelf Side View
at Back Side
of Rear Door
3mm
to Door
Cabinet
Door
3.5mm
to Door
25mm Thick
Door, 2X
75mm
42mm
550mm Inside, Door to Door
600mm Deep Cabinet
Air Outlet
Air Inlet