beautypg.com

2 connecting the cables – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual

Page 79

background image

System Installation

AXP 1410 Installation and Use (6806800H70L)

79

4. Tighten all screws using a torque setting of 35.5 to 38.5 inch-pounds.

Installation in a 600 mm ETSI Rack/Cabinet

The shelf mounts directly from the integrated flange on the front of the shelf.

1. Locate the standard mounting hole and slot locations on the front integrated

mounting flanges on the AXP 1410 shelf.

2. Fasten the mounting brackets to the back side of the front chassis flanges using M6

screws x 12mm at each of the 5 locations.

3. Be sure to mount the shelf with metal screws or bolts that give a good electrical

connection between the screws or bolts and the mounting surface.

4. Tighten all screws using a torque setting of 35.5 to 38.5 inch-pounds.

3.3.2

Connecting the Cables

Failure to observe proper grounding practices may cause a variety of noise, electrostatic
discharge, and RFI (Radio Frequency Interference) problems.

Failure to observe proper grounding practices may cause a variety of noise, electrostatic
discharge, and RFI (Radio Frequency Interference) problems.

This manual is related to the following products: