beautypg.com

3 requirements, 1 environmental requirements, Table 2-1 – Artesyn Centellis 4410 (AXP-1410) Installation and Use (July 2014) User Manual

Page 65: Environmental conditions

background image

Site Preparation

AXP 1410 Installation and Use (6806800H70L)

65

2.3

Requirements

Before and during system installation and operation, you always have to ensure that the
requirements listed in the following sections are met.

2.3.1

Environmental Requirements

To ensure proper function of the system, make sure that the environment in which the system
is to be used fulfills the environmental requirements.

The environmental values must be tested and proven in the planned system configuration, that
means the delivered system and other third-party products you want to integrate.

The following table lists the environmental requirements.

Operating temperatures refer to the temperature of the air circulating at the air intake of the
system and not to component temperatures.

Some of the climatic values may exceed the specification of some system components (for
example hard disks). As Artesyn Embedded Technologies cannot guarantee the functionality
of third party products that are handled or operated out of their specifications, the
environmental conditions may be limited to the specifications of these components.

Table 2-1 Environmental Conditions

Feature

Operating

Non-Operating (packed state)

Temperature

+5ºC (41°F) to +40ºC (104°F) (normal
operation)
according to NEBS standard GR-63-CORE
-5°C (23°F) to +55°C (131°F) (exceptional
operation)
according to NEBS standard GR-63-CORE

-40°C (-40°F) to +70°C (158°F)

Temp.
change

+/-0.25°C/min
according to NEBS standard GR-63-CORE

+/-0.25°C/min

Relative
humidity

5% to 90% non-condensing
according to Artesyn Embedded
Technologies-internal environmental
requirements

5% to 95% non-condensing
according to Artesyn Embedded
Technologies-internal environmental
requirements

This manual is related to the following products: