ReFlex Power™ Programming Manual

DC Module Remote Programming

64

M380056-03 Rev M

3.10

INPUT SCPI COMMANDS

3.10.1

INPUT

SCPI

C

OMMAND

S

UMMARY

INPut

:MENAble:MODE
:MENAble:MODE?

:STATE?

3.10.2

INPUT

SCPI

C

OMMAND

R

EFERENCE

Command

Description

INPut

:MENAble:MODE

0 = Allows the Module ENAble signal to turn the DC supply back On,
only if it was faulted off by Module ENAble going false. (Default
setting) If the supply was off by Module ENAble, and a *RST is
issued, the DC supply will not turn on, unless a OUTP:STAT 1
command is issued.
1 = Prevents the Module ENAble signal from turning the DC supply
On. An OUTP:STAT 1 is required to turn the supply back on.
2 = Module ENAble will always try to turn on the DC supply when it
goes from Off to On. Note: Settings are automatically saved.

:MENAble:MODE?

Query the Module ENAble MODE setting. Default is 0.

:MENAble:STATE?

1 = The Hardware Module ENAble signal is asserted, the module can
be turned On.

0 = When the Hardware Module ENAble is false; the module is Off.

Note: The usage of the

OUTPut:MODFault On

command will temporarily disable

the operation of the

INPut:MENA:MODE

command while it’s active.