AMETEK ReFlex Programming Manual User Manual
Page 43

Controller Module Remote Programming
ReFlex Power™ Programming Manual
M380056-03 Rev L
39
•
If nothing is entered, the default global command is automatically selected, if
the global context can be logically correct.
Required input parameters are enclosed by left and right less-than /
greater-than brackets: < > in the format indicated. For example:
•
•
•
Representation, e.g., zero, positive and negative floating
point numeric values.
•
and negative integer numeric values.
•
indicates Trigger channel input/output connections
(applies only to Controller and programmable DC
modules; see the Trigger command section of this
manual for further details on the
The shorthand version of a command is indicated by capital letters
(minimum required components of a command). For example, SOURce
•
SOURCE
//set output voltage to 120.0V
•
SOUR
//set output voltage to 120.0V
•
SOUR
//set output voltage to 120.0V
2.8.4
Q
UERY
S
YNTAX
The query syntax is identical to the command syntax, but with a question mark
(?) replacing the command’s argument. For example, to query the
programmed output voltage on a Module at address 1, send the command,
SOUR1:VOLT?
. A Module number is required. A value such as 65.00 will be
returned when read.
The ReFlex Power™ Controller requires all commands received to be
terminated with any combination of CR (0x0D), and or LF (0x0A). All
responses are terminated by default with CR/LF (0x0D 0x0A). Response
termination can be changed by using SYST:NET:TERM
user connection is always initializes to CR/LF.