beautypg.com

Echelon NodeBuilder FX User Manual

Page 97

background image

NodeBuilder FX User's Guide

83

8. Specify the following properties:

Project Name

The name of the project as specified in the Specify New Project
Name
dialog. This is a read-only field.

Location

The location of the project folder as specified in the Specify New
Project Name
dialog. This is a read-only field.

Default Transceiver
Type

The transceiver type to be used for Hardware Templates that specify
“default” for the transceiver type. The default transceiver type is
TP/FT-10. See the Using Hardware Templates section in Chapter 5
for more information on hardware templates.

Include Search
Path

An optional semi-colon separated list of directories to be searched for
include files when a NodeBuilder project is compiled. By default,
only the device template source file and the Neuron C standard
include file directories will be searched for include files. If relative
path names are specified, they are relative to the location of the
NodeBuilder project directory (location of the .NbPrj project file).
Note that this list applies to the entire project. By default, this
property is blank.

Run Device
Template Wizard

Automatically opens the Device Template Wizard immediately after
you click Finish. The Device Template Wizard guides you through
the process of creating the first NodeBuilder device template for this
project. See Creating Device Templates in Chapter 5 for more
information. This option is selected by default.

9. Click Finish. If you selected the Run Device Template Wizard check box in the Specify

Project Default Settings dialog, the Device Template Wizard opens. Proceed to the Specifying
the Device Template Name
s