Wiring diagram option identification – Reznor RECC Unit Installation Manual User Manual
Page 73

Form I-MAPSIII&IV, P/N 222917R9, Page 73
Wiring Diagram Option Identification
The Option Codes for these electrical options are shown on the wiring diagram.
Option Brief Description
Installed
AG70
Modulating Gas Control
Factory
AK5
208/3 Supply Voltage
Factory
AK6
230/3 Supply Voltage
Factory
AK7
460/3 Supply Voltage
Factory
AK8
575/3 Supply Voltage
Factory
AN2
Contactor
Factory
AN10
Motor Starter
Factory
ARD3
Motorized Intake Damper (for Option ER)
Factory
AR8
Two-Position (open/closed) O/A Damper
Factory
AR25
Modulating OA/RA Dampers requires Option GF control
Factory
AR2D
Motorized Outside Air Damper and cabinet opening for
power exhaust (Option PE)
Factory
AR2G
Modulating OA/RA Dampers (requires Option GF control)
w/gravity exhaust hood & damper
Factory
AR2H
Modulating OA/RA Dampers (requires Option GF control)
w/exhaust opening in cabinet
Factory
AR2K
Outside Air w/3-position damper, Return/Exhaust Air
w/3-position damper (MAPS
®
unit), gravity damper on
exhaust outlet
Factory
AR2L
100% Outside Air - on/off inlet damper; gravity damper
on exhaust outlet
Factory
AUC9
Hot Gas Bypass
Factory
AUR1
Modulating Reheat
Factory
BA6
Unit flush mounted disconnect on/off switch
Factory
BA7
Dual Disconnects for Emergency - Cab C
Factory
BC2
Convenience Outlet (requires separate power supply)
Fld&Fctry
BD5
Firestat, 200°F (field installed)
Field
BE6
Return Air Temperature & Humidity Sensors
(Opt ER1_) Factory
BE9
Monitors Temperature from Evaporator Coil
Factory
BE10
Monitors Mixed Air Temperature
Factory
BE11
Monitors Duct Static Pressure
Fld&Fctry
BE12
Monitors Building Static Pressure
Fld&Fctry
BE13
Return Air Temperature Sensor
Field
BE14
Return Air Humidity Sensor
Field
BE15
Space CO2 Sensor
Fld&Fctry
BE16
DDC Monitoring Dirty Filter Switch
Factory
BE17
Photoelectric Smoke Detector
Field
BE18
Dirty Filter Pressure Switch
Factory
BE19
OA/RA Override (requires BHB6)
Fld&Fctry
BE20
Manual Schedule Override
Factory
BE21
Contacts only for Occupied/Unoccupied Switch
Factory
BE28
Dirty Filter Switch (for Option ER1)
Factory
BG9
Exhaust Fan Relay
Fld&Fctry
BHB5
Lon Communication Plugin Module
Factory
BHB6
Add'l Inputs & Outputs for Main Controller
Fld&Fctry
BHC5
LON card for Option ER1
Factory
BP4
High and Low Gas Pressure Switches
Factory
BW5D
DDC Monitored Dirty Filter Sensor
Fld&Fctry
CL77
Space Temperature Sensor/Override
Field
CP__
Disconnect Switch
Field
D15
Neutral Air/Discharge Air Temperature Control
Fld&Fctry
D16
Space Temperature Control w/Discharge Air Reset
Fld&Fctry
D17
RECC - Neutral Air/Discharge Air Temperature Control
Fld&Fctry
D18
RECC - Space Temperature Cntrl w/Discharge Air Reset
Fld&Fctry
DT7
Space Relative Humidity Sensor/Control
Field
EFA_
Exhaust Fan Motor HP (for Opt ER1_)
Factory
Option Brief Description
Installed
EFC4
Building Pressure Control for EFD1 (for Opt ER1_)
Fld & Fctry
EFC7
Proportional to MAPS
®
Control for EFD1 (for Opt ER1_)
Factory
EFC9
Adjustable Constant Volume Control for EFD1 (ER1_)
Factory
EFD1
Exhaust Fan Motor Variable Frequency Drive (ER1_)
Factory
EFD2
Variable Frequency Drive (for PE Options)
Field
EG1
Single stage control - RECB, REDB
Factory
EG3
Multi stage control - RECB, REDB
Factory
EL_
Exhaust Fan Motor Type (for Option ER1_)
Factory
EM_
Exhaust Fan Drive (for Option ER1_)
Factory
EN2
Contactor (for Option PE or ER1_)
Factory
EN10
Starter (for Option or ER1_)
Factory
ER1_
Energy Recovery Module
Field
GF1
DDC Damper Control with Remote Manual Potentiometer
(0-5V input signal)
Fld&Fctry
GF2
DDC Two-Position Damper Control
Fld&Fctry
GF4
DDC Four-Position Damper Control based on two input
switches
Fld&Fctry
GF5
DDC Damper Control with Building Pressure Monitor
Fld&Fctry
GF6
DDC Damper Control with Mixed CO2 Control (0-2000
ppm)
Fld&Fctry
GF7
DDC Damper Control with 2-Position Enthalpy Control
Fld&Fctry
GF8
DDC Damper Control with Dual Reference Enthalpy Control Fld&Fctry
GF9
DDC Damper Control with Dry Bulb Mixed Air Economizer Fld&Fctry
JHT1
Additional electrical components required for curb furnace
JH25 (applies to RDCB/RDDB 500MBH)
Factory
JHT2
Additional electrical components required for curb furnace
JH30 (applies to RDCB/RDDB Cabinet C 1000 MBH)
Factory
PE_
Power Exhaust
Fld&Fctry
PL4
Redundant phase loss/reversal protection & high/low
voltage
Factory
RB3
Remote Module with Display, Controls, and Alarm Light
Field
RB4
Hand held control access with 12-ft cable and alarm light
Field
SA1
Duct Photoelectric Smoke Detector
Fld&Fctry
SFA_
Supply Fan Motor HP (for Option ER1_)
Factory
SFC3
Neutral Pressure Control for SFD1 (for Option ER1_)
Factory
SFC9
Adjustable Constant Volume Control for SFD1 (ER1_)
Factory
SFD1
Supply Fan Motor Variable Frequency Drive (ER1_)
Factory
SL_
Supply Fan Motor Type (for Option ER1_)
Factory
SN2
Supply Fan Contactor (for Option ER1_)
Factory
SN10
Supply Fan Starter (for Option ER1_)
Factory
VFC2
Variable Frequency Drive DDC External Control 0-5V Input
(requires BHB6)
Fld&Fctry
VFC3
VFD Duct Static Pressure Control (0 to 2.5" w.c.)
Fld&Fctry
VFC4
VFD Building Static Pressure Control (-0.5 to 0.5)
Fld&Fctry
VFC5
Variable Frequency Drive Space CO2 Control (0-2000 ppm) Fld&Fctry
VFC7
Variable Frequency Drive 3-Speed Wall-Mounted Control
Fld&Fctry
VFC8
Variable Frequency Drive 4-Speed Wall-Mounted Control
Fld&Fctry
VFC9
Adjustable Constant Volume Control
Fld&Fctry
VFD2
Variable Frequency Drive
Field
VFD3
Variable Frequency Drive field provided
Factory
- REDB Unit Installation Manual RECB Unit Installation Manual RDDC Unit Installation Manual RDCC Unit Installation Manual RDDB Unit Installation Manual RDCB Unit Installation Manual RDC Unit Installation Manual RCC Unit Installation Manual RDB Unit Installation Manual RCB Unit Installation Manual REDC Unit Installation Manual MAPSIV Unit Installation Manual MAPSIII Unit Installation Manual