beautypg.com

2 supply fan (blower) start/stop control, 2 supply fan (blower) start/ stop control – Reznor RECC Unit Installation Manual User Manual

Page 49

background image

Form I-MAPSIII&IV, P/N 222917R9, Page 49

CAUTION: The same ground reference has to be used for the CO

2

sensor and for the control

system.

Option BE18, Dirty

Filter Switch

All "C" Cabinet systems have either 2" or 4" pleated disposable or permanent filters. D

Cabinet systems have 4" pleated disposable or permanent filters. If dirty filter indicator

Option BE18 was ordered, a dirty filter switch is in the electrical compartment with tub-

ing sensors placed on either side of the filters as shown in

FIGURE 25.

The pressure switch is in the low voltage electrical compartment. Follow the instruc-

tions in

FIGURE 28F to set the dirty filter switch.

FIGURE 28F -

Dirty Filter Switch,

P/N 105507

Setscrew (on front of switch)

must be manually adjusted after

the system is in operation.

Negative pressure

connection is toward the

"front or top" of the switch

(senses blower side of filters)

Positive pressure

connection is toward the

"back or bottom" of the

switch (senses air inlet

side of filters)

Instructions for Setting Dirty Filter Switch -

With clean filters in place; all doors closed (except

electrical compartment); and the blower operat-

ing, increase the pressure setting by adjusting

the setscrew on the switch clockwise until the

filter light is energized or the screw is bottomed

out. At that point, adjust the setscrew three full

turns counterclockwise or until the screw is top-

ended. At that setpoint, the filter light will be acti-

vated at approximately 50% filter blockage.

Option BE17,

Photoelectric Duct

Smoke Detector

FIGURE 28G - Wiring

Connections for Option

BE17 Photoelectric

Duct Smoke Detector

24V

9

C

10

NC

SMOKE DETECTOR

6

16

The photoelectric smoke detector (

P/N 159553) used in Option BE17 is field mounted

on the ductwork. A field-supplied duct air sampling tube is required. Follow the manu-

facturer's installation instructions. Comply with the requirements in Paragraph 8.1.1

when running the sensor wire. Wires will connect to the controller expansion board.

Refer to the unit wiring diagram.

8.2 Supply Fan

(blower) Start/

Stop Control

The I/Q control can be programmed to operate the unit in two modes: Occupied and

Unoccupied
The supply fan (blower) starts/stops automatically through a local time of day schedule

or remote contact closure commanding the system to occupied mode. If the controller

is connected to a building automation system, other external controllers can control the

mode of operation.
Upon a command for occupied mode, the supply fan starts and runs continuously.

There is a differential pressure (air proving) switch that indicates proof of fan operation.

The supply fan is subject to safety devices, such as duct high limit switches, fire alarm

relays, smoke detectors, low temperature limits, fan status and others devices which

can turn the supply fan OFF.
The control could be programmed with an optional optimum start sequence, which

allows the supply fan to operate and bring the space temperature to its setpoint value

just before the unit is scheduled to be in occupied mode.
If the unit is in the unoccupied mode, the supply fan is turned OFF and will only run

intermittently to maintain night setback/setup space conditions. During the unoccupied

mode, if the override push button on the user wall interface is pressed, the unit will

switch to occupied mode for 60 minutes.

Control Mode (Default = Stand alone): Stand alone or BAS

Push Button Override Timer (Default=60 minutes): Range=15 minutes to 240 minutes
Hardwire Occupancy Input (Default = Disabled): Enabled or Disabled
Optimum Start/Stop (Default=Enabled): Enabled or Disabled
NOTE: The hardwired occupancy input will override the local or remote schedule. If

this point is active, the software schedules do not function.
Optional Supply Fan Controls: Optional variable frequency drive (Option VFD) can be

controlled by a number of optional sensors.

Adjustable Control

Parameters from Local

Display (in the control

compartment) and

Remote Display (if

equipped)