6 condenser fan motors and fans, 7 compressors, 0 electrical and wiring (cont'd) – Reznor RECC Unit Installation Manual User Manual
Page 44

Form I-MAPSIII&IV, Page 44
7.6 Condenser Fan Motors and Fans
All condenser fan motors are direct-drive, statically and dynamically balanced, and
permanently lubricated. Condenser fan motors are open dripproof motors with exter-
nal sling protection against water penetration and have auto reset thermal overload
protection.
Area above the fans should always be unrestricted and open.
7.7 Compressors
All of the compressors are high efficiency hermetic scroll type designed for use with
R-410A refrigerant. Circuit A, B, C, and D cooling compressors are in the Compressor
Section. Circuit E or Dh compressor (reheat) is located in the cabinet filter section.
Compressor
Model
ARI
Tonnage
208 V
230 V
460 V
575 V
RLA
LRA
RLA
LRA
RLA
LRA
RLA
LRA
ZP24K5E
2
9.6
58.0
9.6
58.0
5.1
28.0
3.3
23.7
ZP36K5E
3
13.5
88.0
13.5
88.0
6.0
44.0
4.9
34.0
ZP54K5E
4.5
15.6
110
15.6
110
7.8
52
5.8
38.9
ZP57K3E
5
20.5
155
20.5
155
9.6
75
7.6
54
ZP61KCE
5
19.0
123
19.0
123
9.7
62
7.4
50
ZPD61KCE
5
20.4
156
20.4
156
9.7
62
7.4
50
ZP72KCE
6
23.2
164
23.2
164
11.2
75
7.9
54
ZP83KCE
7
25.0
164
25.0
164
12.2
100
9.0
78
ZPD83KCE
7
24.0
187
24.0
187
12.6
100
9.9
78
ZP120KCE
10
33.3
239
33.3
239
17.9
125
12.8
80
ZP137KCE
11
48.1
245
48.1
245
18.6
125
14.7
100
ZPD137KCE
11.4
48.1
245
48.1
245
18.6
125
14.7
100
ZPT144KCE
12T
23.2
164
23.2
164
11.2
75
7.9
54
ZP154KCE
12
51.3
300
51.3
300
23.1
150
19.9
109
ZPDT14MCE
12
46.4
164
46.4
164
22.4
75
15.8
54
ZP182KCE
15
55.8
340
55.8
340
26.9
173
23.7
132
Compressor Amps/
Voltage
7.0 Electrical and
Wiring (cont'd)
(For additional information,
refer to the Operation/
Maintenance/Service
Manual, either Form
O-MAPS Cabinets A/B/C or
Form O-MAPS Cabinet D)
Mechanical Compressor Protection - A low pressure cutoff (LPCO) switch is used for
protection against compressor damage due to a loss of system charge. This protection
prevents short cycling on the internal overload (IOL) which can pump the oil out of the
compressor.
All compressors also have manual reset high pressure cutouts (HPCO) and frost
stats.
Compressor Staging (RCB, RDB, RDCB, RDDB, RECB. REDB) - Each system
leaves the factory with the compressor staging sequence set. The compressor will
start based upon a call for cooling to maintain the discharge air temperature setpoint.
There is a minimum 240 second ON and OFF time for each stage (not compressor).
Compressor Modulation (RCC, RDC, RDCC, RDDC, RECC. REDC) - These units
have scroll compressors equipped with modulating valves and a digital controller that
interfaces the compressor with the system controller. Compressor operation will start
based upon a call for cooling and will modulate to maintain the discharge air tempera-
ture setpoint. There is a five-minute compressor on/off time.
For additional information about compressor operation, see the Operation/Mainte-
nance/Service Manual.
Crankcase Heaters - Each compressor has a band-type crankcase heater. Crankcase
heaters must always be energized for at last 24 hours prior to operating the compres-
sor.
If ordered with Option AUC9, the bypass valve will provide expanded compressor
modulation at low outside air temperatures by allowing some of the gas from the suc-
tion line to be re-routed directly to the evaporator coil. With Option AUC9, at least one
circuit per stage has a hot gas bypass valve.
Hot gas bypass valves are factory set. However, the factory setting should be checked
at startup. To check the valve operation and/or make field adjustments, it is necessary
to simulate a light load condition as described below.
Optional Hot Gas
Bypass
Condenser Fan Control
1. The unit has a maximum of four condenser fans.
2. The condenser fans are electrically tied to the compressors.
3. The condenser fans on "D" Cabinet systems are grouped into two banks.
- REDB Unit Installation Manual RECB Unit Installation Manual RDDC Unit Installation Manual RDCC Unit Installation Manual RDDB Unit Installation Manual RDCB Unit Installation Manual RDC Unit Installation Manual RCC Unit Installation Manual RDB Unit Installation Manual RCB Unit Installation Manual REDC Unit Installation Manual MAPSIV Unit Installation Manual MAPSIII Unit Installation Manual