beautypg.com

0 controls (cont'd) – Reznor RECC Unit Installation Manual User Manual

Page 46

background image

Form I-MAPSIII&IV, Page 46

Outside

Air

Return

Air

Mixed Air Averaging

Sensor (between

filters and coil)

Return Air

Sensor

Temperature/

Humidity

Outside

Air Sensor

Temperature/

Humidity

Filters

Dirty Filter Switch Sensor

(entering air side)

Dirty Filter Switch Sensor

(leaving air side)

Coils

Air Proving

Switch Tap

Heat

Section

Discharge Temperature

Sensor (field installed;

see Paragraph 8.1.1)

Discharge

Temperature

Sensor (field

installed; see

Paragraph

8.1.1)

Vertical

Discharge

Horizontal

Discharge

Condenser Section

FIGURE 25 - Airflow and Sensor (std & some optional) Locations - D Cabinet

illustrated

8.1.1 Instructions for

Installing Discharge

Air Sensor in the

Ductwork

FIGURE 26 -

Discharge Air

Temperature

Sensor Probe and

Weatherproof Box,

P/N 222753

The discharge air temperature sensor (See

FIGURE 26.) is shipped with every unit

and must be field installed in the ductwork. The location and position of the sensor are

important. Follow the instructions below.
1. Determine the appropriate distance from the unit. Be sure there is sufficient

distance from the outlet to have a good mixture of discharge air temperature.

According to the latest edition of AMCA Standard 201, in straight ducts, the air

is typically well mixed a minimum of five equivalent duct diameters from the dis-

charge of the unit with equivalent duct diameter defined as equal to the square

root of 4AB/3.14. "A" and "B" are the duct cross-sectional dimensions.

Example: Supply ductwork cross-sectional dimension is

24" x 12" (610mm x 305mm).

5 x

4 x 12 x 24

3.14

= 96"

5 x

4 x 305 x 610

3.14

= 2435mm

Locate the sensor a minimum of 96" (2435mm) from the

outlet of the unit.

NOTE: If the length of the discharge duct is less than 8 ft (2.4M), a mixing vane is

recommended for mixing the discharge air.

Do not mount the sensor in the ductwork after a split in the supply as that will

cause loss of control in the duct that does not house the sensor.

2. Determine the location and orientation of the sensor. The position of the sen-

sor in the duct is also important. In horizontal ductwork, locate the sensor assem-

bly in the top, middle of the duct with the sensor probe extending vertically down

into the center of the airstream.

In vertical ductwork, locate the sensor assembly in the middle of the side of the

duct that corresponds with the top middle of the discharge outlet.

3. Attach the sensor. Mark the selected location and drill a 7/16" hole. Insert the

probe into the hole. Be sure that the blue plastic fitting holding the probe is cen-

tered in the hole. Attach with two No. 8 sheetmetal screws (do not overtighten).

Check to be certain that the hole is sealed.

4. Run the sensor wire to the unit. Use field-supplied 2 to 3 pair of 16 to 22 ga

wire. Digital control inputs are low-current, resistance-based signals. For optimum

temperature control performance, it is recommended that the sensor inputs (zone

8.1 Cooling/ Dehumidification/Heating Control (cont'd)

8.0 Controls

(cont'd)