beautypg.com

Mechanical (cont'd), 3 outside air hood (cont'd), 2 option as16, inlet air hood for maps – Reznor RECC Unit Installation Manual User Manual

Page 34: Iii "d" cabinet, 1 air hoods for maps, Iii a, b, & c cabinets (cont'd), Iii d cabinet

background image

Form I-MAPSIII&IV, Page 34

6.3.2 Option AS16,

Inlet Air Hood for

MAPS

®

III "D" Cabinet

Installation Instructions for Inlet Air Hood Option AS16 for D Cabinet

Models

To avoid possible damage, it is recommended that the outside air hood be installed

after the system has been placed on the roof. The air hood should be installed before

the blower is operated. Do not install the hood while the system is in operation. Due to

the size, assembly and installation requires two persons.

6. Mechanical

(cont'd)

6.3 Outside Air

Hood (cont'd)

Filter

16x20x1

Filter

16x20x1

Filter

16x20x1

Filter

16x25x1

Filter

16x25x1

Filter

16x25x1

Filter

16x20x1

Filter

16x20x1

Filter

16x20x1

Inlet View Showing Filter Arrangement

Top, P/N 255207

(Slide edge of top under cabinet top.)

Top Support,

P/N 208636

V

ertical Filter

Supports,

(2) P/N 208632

Sheetmetal

Screws,

P/N 11813

Right Side,

P/N 208629

Left Side,

P/N 208630

Filter

Angles

(2) P/N

208635

Filter Clamp

(2) P/N 208634

Bottom,

P/N 208631

Clip-on

Receptacle

for Wing Screw

(4) P/N 205708

Nylon Retainer for Wing

Screw (4) P/N 205709

Wing Head Screw

(4) P/N 205707

Top Filter Filler,

P/N 210146

Filter Spacer

(2) P/N 208633

FIGURE 17D - Installation of Outside Air

Hood, Option AS16 or Option AS19, on

MAPS

®

III Cabinet C Models

For a cross-reference of

cabinet size and model size,

refer to the Appendix,

pages 71-72.)

FIGURE 17D - Cabinet Size C with or without a power exhaust option - Attach

the top filter filler, the two vertical filter supports and the two side filter angles.

Attach the two inner filter spacers with wing screw receptacles. Position the nine

filters in the opening as shown. Secure the filters with the filter clamps and the

wing screws.

6.3.1 Air Hoods for MAPS

®

III A, B, & C Cabinets (cont'd)

Installation NOTES:

- Select screws carefully. Use sheetmetal screws (slotted head with straight tip) when holes in the cabinet are

provided. Use self-drilling screws (head is not slotted with drill-type tip) when matching holes are not provided.

- Follow STEPS in order.

FIGURE 18A - Assembled Inlet Air Hood, Option AS16 for MAPS

®

III D Cabinet

48-11/32” (1228mm)

54-1/4”

(1378mm)

6-1/4” (159mm)

Dimension

from top of

unit and

rear panel.

Side View

of Installed

Hood

(2) P/N 104102,

16x16x1

(2) P/N 104102,

16x16x1

(2) P/N 104102,

16x16x1

(2) P/N 104102,

16x16x1

(2) P/N 104102,

16x16x1

(2) P/N 104102,

16x16x1

(2) P/N 101609,

16x25x1

(2) P/N 101609,

16x25x1

(2) P/N 101609,

16x25x1

Inlet View of Installed Hood