beautypg.com

5 rigging and lifting the maps, Units, 0 mounting (cont'd) – Reznor RECC Unit Installation Manual User Manual

Page 28

background image

Form I-MAPSIII&IV, Page 28

Installing Ductwork with

Option CJ3 MAPS

®

III

Cabinet D Roof Curb

The roof curb designed for the MAPS

®

D Cabinet

includes return air and discharge

duct supports that allow the ductwork to be inserted down through the roof. The sizes

of the duct openings are shown in

FIGURE 12E. Ductwork should be sized slightly

smaller with a minimum 3/4" duct flange that can be attached to all sides of the duct

connection. The duct opening is positioned to mate with the heater inlet or discharge.

After installing the ductwork, before placing the system on the curb, apply sealant tape

to the top surface of the duct opening sides making good butt joints at the corners.

(Sealing tape must also be applied to the curb rails.)

47-1

1/16”

(121

1mm)

Unit Airflow

Size of

Discharge

Duct Opening

for inserting

ductwork down

through

the roof curb.

Size of Return

Air Duct

Opening for inserting ductwork down through

the roof curb.

19-7/8”

(505mm)

26-3/4”

(679mm)

72” (1829mm)

4-7/16”

(113mm)

12-9/16”

(319mm)

35-21/32” (906mm)

4-1/2”

(114mm)

12-3/4” (324mm)

Top View

Showing Duct Opening Sizes

and Perimeter only of

Option CJ3 Roof Curb

5-21/32” (144mm)

RCB, RDB, RECB, REDB - All Sizes - 133-5/16” (3386mm)

RDCB, RDDB with Heat Sections 500, 600, 700, 800 - 133-5/16” (3386mm)

RDCB, RDDB with Heat Sections 1000, 1200, 1400, 1600 - 165-3/4” (4210mm)

FIGURE 12E - Duct Opening Dimensions and Locations inside Option CJ3 Roof Curb for

MAPS

®

III Cabinet D

5.0 Mounting

(cont'd)

5.4.4.Roof Curbs for MAPS

®

Models RCB, RDB, RDCB, RDDB,

RECB, REDB Cabinet Size D (cont'd)

5.4 Mounting on a Roof Curb (cont'd)

5.5 Rigging and

Lifting the

MAPS

®

Units

DANGER

If there is any visible damage or any question about the integrity

of a lifting point, DO NOT LIFT the system. Consult the factory.

See approximate net weights in Paragraph 5.1. If corner weights are required, refer to

Sales/Technical Catalog Form C-PC (available at www.RezSpec.com).

IMPORTANT

NOTE: ALL MAPS

®

Cabinet C and D systems MUST be loaded and unloaded by lift-

ing. Due to size, DO NOT attempt to move any MAPS

®

C or D Cabinet with a fork lift.

Holes for attaching rigging are provided in the base. Cabinets A, B, and C have four

lifting holes -- one on each corner; see

FIGURE 14A. Cabinet D has six lifting holes for

rigging; see

FIGURE 14B. ALL lifting points MUST always be used. Spreader bars

MUST be used to prevent cabinet damage.

Failure to lift by the manufacturer's instructions could cause damage to the equipment

and/or personal injury or death. The equipment manufacturer is not responsible for

unsafe rigging or lifting procedures.
The unit MUST be rigged with spreader bars that will allow the unit to be lifted straight

up with vertical force only on the lifting points. Using ALL lifting points is mandatory.
In addition to checking the rigging, before lifting the unit, verify the following:

If the unit is being set on a down discharge curb and ductwork is being installed

from the top, verify that the ductwork is installed.

If installing an Option JH duct furnace curb section, verify that sealant tape has

been applied to all top surfaces of the curb. Verify the orientation so that the

openings match. Set the duct furnace section on the roof curb before the unit.