background image

Form I-MAPSIII&IV, Page 4

Massachusetts

Requirements

If being installed in the Commonwealth of Massachusetts, this unit must be installed by

a licensed plumber or licensed gas fitter.

California Warning

Label

If a gas-fired heat section is included and the system is being installed in the state of

California, the installer MUST attach the warning label on the outside of the heat sec-

tion access panel. The California Warning label is shipped in the "Literature Bag". If

installation is in California, select a dry, clean location on the heat section access panel

and adhere the label.

3.0 Receiving and

Storage

1.0 General

(cont'd)

1.4 Installation Codes

These packaged systems are certified by ETL to "Heating Cooling Equipment" (latest

edition), UL 1995 / CAN/CSA C22.2 No. 236-05. Electrical characteristics are shown

on the system rating plate. All cooling and re-heat pump reheat cycle circuits are fac-

tory-charged with R-410A refrigerant.
Models RDCB, RDDB, RDCC, and RDDC include a single or double gas heat sec-

tion. The gas-fired, power-vented duct furnace uses the Reznor

®

TCORE

combustion

system. The heat section is available in nine sizes from 400 to 1600 MBH for use with

natural gas. The furnace is certified by ETL to the latest editions of both ANSI Z83.8

and CSA 2.6 for use in the United States and Canada. The ETL label, type of gas, and

the firing rate are shown on the heat section rating plate.

Approval and

Installation Codes

2.0 Location and

Moving

This outdoor unit is designed to be set on a slab, on a roof curb, or on rails (D Cabinet)

and must be level for proper operation. When selecting the location, check the follow-

ing:

Installation location must comply with local codes.

Location on a roof depends on building structure. Refer to the weights in

Paragraph 5.1.

Comply with required clearances in Paragraph 4.1.

Position the unit so that the outside air inlet will not be facing into the prevailing

wind.

Before moving unit, refer to Paragraph 5.6 for rigging information. See

NOTE on

left.

3.1 Receiving

This system was test operated and inspected at the factory and was in operating con-

dition. If the equipment has incurred any damage in shipment, document the damage

with the carrier and immediately contact your Reznor

®

distributor.

Check the entire unit for damage paying particular attention to the structural integrity of

the lifting points and the condenser fan section. Check the condenser fan guards and

the fan blades.
On the inside of the door of the control compartment, locate the system rating plate

(See

FIGURE 1A.). Check the specifications and the electrical characteristics and ver-

ify compatibility with the electric supply at the installation site.
If installing a MAPS

®

unit with a heat section, check the rating plate (See

FIGURE

1B.) on the inside cover of the heat section. Be sure that the rating plate information is

compatible with the electric and/or gas supply at the installation site.

Check for shipped-separate accessories and shipped-loose parts. All systems will

have a shipped-loose discharge air sensor. The roof curb is shipped separately (See

Paragraph 5.2), and in most cases, in advance of the unit. The outside air hood is

shipped in a separate carton for field assembly and installation. (

NOTE: Install the

hood after the unit is in place.) An optional energy recovery module is shipped as a

separate component to be mated to the unit at the installation site.

If ordered, other items that would be shipped separately include a disconnect switch,

various types of space-mounted sensors and controls, a duct smoke detector, a VFD,

a firestat, extra belts, and extra filters.

Shipped-Separate

Accessories and

Shipped-Loose Parts

IMPORTANT NOTE: A

Cabinet Size C or D unit

MUST be loaded and

unloaded using ALL lifting

points and spreader bars.

DO NOT attempt to move

a MAPS

®

Cabinet Size C

or D with a fork lift.