beautypg.com

2 storage, 0 clearances and dimensions, 1 clearances – Reznor RECC Unit Installation Manual User Manual

Page 6: 0 receiving and storage (cont'd)

background image

Form I-MAPSIII&IV, Page 6

4.0 Clearances

and

Dimensions

3.2 Storage

If this system is going to be stored, take precautions to prevent condensate formation

inside the electrical compartments and motors. To prevent damage to the unit, do not

store sitting on the ground.

Battery backup for controls will maintain for approximately one year. If backup expires,

controls will need to be reprogrammed.

3.0 Receiving

and Storage

(cont'd)

Provide minimum clearances as shown in

FIGURE 2A or 2B. Minimum clearances

are required to ensure proper operation and access for service. If a heat section is

included, clearance to combustibles is required. Clearance to combustibles is defined

as the minimum distance from the heater to a surface or object that is necessary to

ensure that a surface temperature of 90°F (50°C) above the surrounding ambient tem-

perature is not exceeded.

4.1 Clearances

FIGURE 2A - MAPS

®

A, B, & C Cabinet Clearances

For cross-reference of cabinet size to model

size, see APPENDIX, pages 71-72.

Top Clearance: All Models - 60"

(1524mm)

Bottom Clearance: All Models - 0"

(0mm)

Additional Gas Heat Section

Clearance Information

If installing a unit with a gas heat

section, the 40" (1016mm) service

clearance provides for clearance to

combustibles and required space for

combustion air inlet and venting. Vent

terminal must be 4 feet (1.22M) from

gas and electric meters, regulators,

and relief equipment.

FIGURE 2B - MAPS

®

III D Cabinet Clearances

For cross-reference of cabinet size to model

size, see APPENDIX, pages 71-72.

Top Clearance: All Models - 60"

(1524mm)

Bottom Clearance: All Models - 0"

(0mm)

Additional Gas Heat Section

Clearance Information -

If installing a unit with a gas heat

section, the 4 ft 7 inch (1.4M)

service clearance provides for

clearance to combustibles and

required space for combustion air

inlet and venting. Vent terminal

must be 4 feet (1.22M) from gas

and electric meters, regulators,

and relief equipment.

Bottom Supply

Air Opening

Bottom Return Air Opening

Outside Air

Hood

Top View

Airflow

All Models with

gas or electric heat

- Clearance to

Combustibles -

4 ft (1.22M)

Models RDCB, RDCC,

RDDB & RDDC -

Service Clearance is

4 ft 7 inches (1.4M)

Models RECB, RECC,

REDB & REDC

- Service Clearance

is 4 ft (1.22M)

Door Width (largest door)

Cabinet A, 23” (584mm)

Cabinet B, 27“ (686mm)

Cabinet C, 32” (813mm)

Door Width (largest door)

Cabinets A&B, 26” (660mm)

Cabinet C, 32-1/2” (826mm)

All Models - Minimum Service

Clearance - Width of the Unit

All Models - 24” (610mm)

All Models - 24” (610mm)

Outside

Air Hood,

Option

AS16

All Models - 24” (610mm)

All Models - 24” (610mm)

Models RDCB, RDDB, RECB, REDB - Clearance to

Combustibles - 40” (1016mm)

Models RDCB & RDDB - Service Clearance - 40” (1016mm)

Models RECB & REDB - Service Clearance - 64” (1626mm)

All Models - 87” (2210mm) is minimum clearance

to remove coil section sliding drain pan

Top View

Control

Side

Airflow

All Models - 24” (610mm)

IMPORTANT: The area above the condenser fans MUST ALWAYS be totally open

space to allow proper airflow through the condenser coils.