beautypg.com

0 electrical and wiring (cont'd), 2 supply wiring (cont'd), Warning if the maps – Reznor RECC Unit Installation Manual User Manual

Page 42: 3 3-phase wiring check, 2 supply voltage, Figure 22 - disconnect wiring connections

background image

Form I-MAPSIII&IV, Page 42

FIGURE 22 - Disconnect

Wiring Connections

BLACK

BLACK

L3

T3

GRD

L1

T1

L2

T2

Field-supplied or

Option CP

Disconnect

Switch

Field-supplied or

Option CP

Disconnect Switch

Unit-Mounted Option BA6 ON/OFF

Lockable Disconnect Switch

(Non-fusible, available only

with 460/3 or 575/3 supply)

Supply V

oltage

(See MCA

on rating plate to determine wire size.)

Supply V

oltage

(See MCA

on rating plate to determine wire size.)

YELLOW

YELLOW

RED

RED

Field

Factory

GRD

G

L1

L2

L3

(No Option BA6)

Option BA6 requires copper wiring with

ampacity based on 75°C maximum temp-

erature rating at the line side terminals.

WARNING

If the MAPS

®

unit includes a gas furnace, always turn off the gas when you turn off the

power supply.

7.0 Electrical and

Wiring (cont'd)

7.2 Supply Wiring

(cont'd)

7.2.3 3-Phase Wiring

Check

3-Phase Wiring Connection - There is a chance of unknowingly connecting

3-phase power in such a way as to cause compressor and blower rotation in

reverse. To prevent damage to the components, it is important to check this on

startup.

7.2.2 Supply Voltage

The electric supply to the unit must meet stringent requirements for the system to oper-

ate properly. Voltage supply should be within ±10% or as stated on the rating plate.
Maximum imbalance on a 3-phase system is 2%.
If the power supply is not within these tolerances, contact the power company prior to

operating the system.

CAUTION: If this unit is allowed to operate on an electric supply

that is not within the specified tolerances, the product warranty

shall be void.

Follow instructions below to check.
Check Voltage Supply - See voltage use range on the rating plate. Measure (and

record) each supply leg voltage at all line disconnect switches. Readings must fall

within the allowable range.
Check Voltage Imbalance - In a 3-phase system, excessive voltage imbalance

between phases will cause compressor motors to overheat and eventually fail. Maxi-

mum allowable imbalance is 2%. To determine voltage imbalance, use recorded volt-

age measurements taken above in the following formula.
NOTE: If the unit is equipped with Option PL4, an over/under voltage protection device,

the unit will shut down on an over or under voltage supply condition and also if there

is a phase loss. This is an auto reset device and will reset when the power condition

is corrected.

Key:

V1, V2, V3 = line voltages as measured

VA (average) =

(V1 + V2 + V3)

3

VD = line voltage (V1, V2, or V3) that deviates farthest from average (VA)

Formula:

% Line Voltage Imbalance =

[100 x (VA - VD)]

VA

Optional Voltage Protection, Option PL4 - If the system was ordered with Option

PL4 (identified on the wiring diagram), it will have a factory-installed redundant phase

loss/reversal and over/under voltage monitor. The monitor will cause the controller to

shut down the unit until the power condition is corrected. It is an automatic reset device.