beautypg.com

Reznor RECC Unit Installation Manual User Manual

Page 61

background image

Form I-MAPSIII&IV, P/N 222917R9, Page 61

Normal Furnace Operation Display - MAPS

®

Cabinets A, B, and C

LED Display

Heat Mode

Description

OFF Mode (OFF) System Idle - Control board has power, no faults found, no call for heat.
PURGE Mode

(Pur)

System is purging the heat exchanger – No gas on, no flame, venter motor runs for the speci-

fied purge timings. Purge cycles occur immediately before and after each burner operation.

IGNITION Mode

(Ign)

System is initiating burner operation – Ignitor energized, modulating valve moved to

ignition setting, gas on. Maintained for the trial-for-ignition period and the five-second flame

stabilization period.

WARM-UP Mode

(HEA)

Period between Ignition and Run – System checks completed before modulation control

begins.

RUN Mode (run) Normal modulating operation.
Ignition Retry

(rEt)

System has had a failed ignition attempt or has lost flame during burner operation and is

beginning another ignition cycle.

Cabinets A and B have the same module but a unique ID plug for each heat section

(Cabinet A Heat Sections 100, 150, 200; Cabinet B Heat Sections 250 and 300).
The module has a three-digit LED display that indicates the active furnace operation.

See the table below for a description of the heat mode identified by each LED display.

For additional information, refer to operation / maintenance manual, Form O-MAPS

Cabinets A/B/C.

9.2.2.2 Ignition System

for "D" Cabinet

Ignition Control System

NOTE: Each of the

individual burner

sizes (500, 600, 700,

and 800) has a unique

control module.

Normal Heat Cycle

Operating Sequence

with Modulating Gas

Control AG70 - "D"

Cabinet only

FIGURE 43A - Control

Module used in

Modulating Gas Control

Option AG70 - "D"

Cabinet only

-

1 GREEN FLASH: Stand-by mode. Ready to accept call for heating.

-

1 AMBER FLASH: Heating cycle initiated; gas OFF.

-

2 AMBER FLASH: Heating cycle initiated, all safety checks passed and

gas ON.

-

5 AMBER FLASHES: Suppressed firing rate due to low combustion air or

high altitude operation.

-

RAPID GREEN FLASH: Indicates furnace was manually put into the test

mode

as it applies to ALL Heat Sections with one furnace (Sizes 500, 600,

700, 800) AND the First (upstream) furnace of Heat Sections with two

furnaces (Sizes 1000, 1200, 1400, 1600) of "D" Cabinet Models

Ignition Control System as it applies to second furnace of Heat Sections

with two furnaces (Sizes 1000, 1200, 1400, 1600) of "D" Cabinet Models

The downstream furnace in a "D" cabinet with two heat sections is equipped with a

direct spark integrated control module (circuit board). The module monitors the safety

devices and controls the operation of the venter motors and the gas valve between

heat cycles.

Normal Heat Cycle Operating Sequence - Downstream Furnace of "D"

Cabinet Sizes 1000, 1200, 1400, 1600

1) Call for Heat - The heating/cooling system controller calls for heat. The ignition

system circuit board checks to see that the limit switch is closed and the pressure

switch is open.