beautypg.com

0 optional equipment, 1 inlet air options, Outside air only dampers, option ar8 or ar2l – Reznor RECC Unit Installation Manual User Manual

Page 53

background image

Form I-MAPSIII&IV, P/N 222917R9, Page 53

Optional Equipment (alphabetically listed) ..................................Where to Look

Air Control Options, Option AR__ ................................................Paragraph 9.1, pages 53-55
Duct Furnace Curb, Model JHUP (Option JH__) ......................Paragraph 5.4.3, pages 23-25
Electric Heat Section (Models RECB/REDB/RECC/REDC) ........Paragraph 9.3, pages 63-64

plus throughout this manual

Energy Recovery, Option ER1 ............. Paragraph 6.1, page 30, plus Form I-MAPSIII&IV-ER
Gas Heat Section (Models RDCB/RDDB/RDCC/RDDC) ...........Paragraph 9.2, pages 55-63

plus throughout this manual

Inlet Air Hood, Option AS16 & AS19 .........Paragraph 6.3, page 32-37, plus Form I-OPT-WH
Power Exhaust, Option PE .................................................................Paragraph 6.2, page 31
Roof Curbs, Options CJ3, CJ31, CJ34,

CJ49, CJ50, CJ53, CJ54 ........................ Paragraph 5.4, pages 10-28, plus Form I-OPT-C

9.0 Optional

Equipment

including Heat

Sections

The system may be equipped with a variety of configurations and air control options

including 100% outside air, outside and return air, a variety of damper controls, and the

field-installed energy recovery module in Paragraph 6.1. Inlet air configurations with

and without dampers are identified as Option AR and may apply to the MAPS

®

unit

only or to a MAPS

®

unit with an energy recovery module. Some inlet air options require

additional Option GF controls. Option AR2D is for use with Option PE power exhaust.
Refer to the

FIGURE 34 to identify the appearance of each inlet air configuration.

9.1 Inlet Air Options

Option AR1 -

100% Outside

Air - Cabinet

A, B, C, or D)

(no factory-

installed

dampers)

Option AR8 -

100% Outside Air

with Motorized

Damper for

Cabinet A, B,

C, or D -

damper opening

interlocked with

blower start

Option AR25 - Outside

Air and Return Air with

Motorized Dampers for

Cabinet A, B, C, or D -

requires factory

or field-installed

control

(Option GF)

Outside

Air

Return Air

Option AR2D - 100%

Outside Air with

Motorized Damper

for Cabinet A, B,

or C with power

exhaust

(Option PE)

Exhaust Air

Outside

Air

(Option PE)

(MAPS unit)

(MAPS unit)

(MAPS unit)

(MAPS unit)

Option AR2G - Outside

Air and Return Air with

Motorized Dampers for

Cabinet A, B, or C

with gravity exhaust

damper and hood -

requires factory

or field-

installed

control

(Option GF)

Outside Air

Return /

Exhaust Air

Gravity

Exhaust

(MAPS unit)

Outside

Air

(MAPS unit)

Option AR2J

on Energy

Recovery

Module

(Option ER1)

Cabinet

A, B, or C

with Option

ER1

Exhaust Air

(Energy

Recovery

Module)

Outside

Air

(MAPS unit)

Option AR2L

on Energy

Recovery

Module

(Option ER1)

Cabinet A, B, or C

with Option ER1

Cabinet A, B, or C

with Option ER1

Exhaust Air

(Energy

Recovery

Module)

Outside

Air

(MAPS unit)

Option AR2K

on Energy

Recovery

Module

(Option ER1)

(Energy

Recovery

Module)

Return /

Exhaust Air

Outside

Air

(MAPS unit)

Option AR2H - Outside

Air and Return Air with

Motorized Dampers for

Cabinet A, B, or C

with gravity exhaust -

requires factory

or field-

installed

control

(Option GF)

Return /

Exhaust Air

Gravity

Exhaust

Damper

Gravity

Exhaust

Damper

Gravity

Exhaust

Damper

100% Outside Air

with Motorized

Damper in ER

module interlocked

with unit blower

start

Outside Air &

Return Air with

interlocked Motor-

ized Dampers -

requires control

Option GF2

or GF7

FIGURE 34 -

Inlet Air

Configurations

by AR Option

Inlet Air Dampers and

Controls

Outside Air Only Dampers, Option AR8 or AR2L

-The damper motor is

electrically interlocked with the blower (supply fan) motor such that a command to start

the fan opens the damper first and then allows the fan to run. When the fan is called to

be OFF, the damper closes.