0 mounting (cont'd), 4 mounting on a roof curb (cont'd), Duct furnace operation – Reznor RECC Unit Installation Manual User Manual
Page 24: Option jh30 duct furnace installation, Remote temperature controller, Form i-mapsiii&iv, page 24

Form I-MAPSIII&IV, Page 24
5.0 Mounting
(cont'd)
5.4.3 Duct Furnace Curb Sections, Option JH30 for Cabinet C and
Option JH25 for Cabinet B (cont'd)
Duct Furnace Operation
The duct furnace can only be energized after the main unit DSI control has enabled
operation of the integral heat section and the remote temperature controller's sensor
initiates a call for heat. When both of these conditions are met, the duct furnace will
be energized to operate at full fire only.
FIGURE 11C - Wiring Connections for Optional Curb Duct Furnace
41
FLAME
ELECTRODES
BR
BK OR R
FLAME GROUND
R
R
BR
R
NEUTRAL
P1-7
P1-9
BL
#2 GAS VALVE
BR
PRESSURE SWITCH
(PS3)
Y
Y
Y
R
P1-4
BL
64
63
BR P1-2
P1-5
P1-3
P1-6
REMOTE TEMPERATURE CONTROLLER
CONTROL TERMINAL IN T7079
DUCT FURNACE ENABLE
RELAY CONTACTS
BK OR R
NO
COM
J4
LIMIT CONTROL
34 R
R
33 R
4
6
R
Y
R
P3-1
P1-8
P3-4
32 Y
P3-2
P3-3
P3-5
DUCT FURNACE ENABLE
RELAY COIL (319)
40
40 BL
7
300
CR
8
BR
41
INTERNAL CONTROL FAULT OR NO POWER
STEADY OFF
(VM2)
MOTOR
VENTER
CAPACITOR
UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)
(DS2)
WEAK FLAME
FLAME SENSED
DSI CONTROL
DUCT FURNACE
FAST FLASH
SLOW FLASH
STEADY ON
YELLOW LED
OK
LED
G
TRANSFORMER
SPARK
Y
LED
FLAME
TEST
NEUTRAL
IND
BR/W
SPARK GAP
BK
W
BR
BK
G
GRD
NORMAL OPERATION CALL FOR HEAT
NORMAL OPERATION NO CALL FOR HEAT
PRESSURE SWITCH DOES NOT CLOSE WITHIN 30
PRESSURE SWITCH IS CLOSED BEFORE VENTER IS
ENERGIZED
IN LOCKOUT FROM FAILED IGNITIONS OR FLAME LOSSES
SW1
LED FLASH CODES
LIMIT SWITCH OPEN
SECONDS OF VENTER ENERGIZED
2 FLASH
1 FLASH
3 FLASH
FAST FLASH
STEADY ON
4 FLASH
Y
R
C
W
G
GREEN LED
3.0 AMP
FUSE
AT
O
OR A
TC
SEC
COM
NEUTRAL
L1
BREAKER
96
Y
CIRCUIT
88
BK
W
(TX5)
97
Y/W
Y/W
24 V
TRANSFORMER
240V
O
GY
R
75 VA
DSI
O
89
BK
L1
L1
L1
SEC
NEUTRAL
COM
W
BL
BR
89
88
BK
BK
88
89
FACTORY WIRING
FIELD WIRING
TERMINAL BLOCK -- DUCT FURNACE
TERMINAL BLOCK -- HIGH VOLTAGE
TERMINAL BLOCK -- LOW VOLTAGE
COMPARTMENT
COMPARTMENT
(See below and unit diagram.)
#1 GAS VALVE
BL
BL
BR
(See unit wiring diagram.)
(See unit wiring diagram.)
SET ST1 SWITCH
TO HEAT POSITION
(MOUNT IN OUTSIDE AIRSTREAM)
TEMPERATURE SENSOR
T7079 REMOTE
TEMPERATURE
CONTROLLER
J1 SENSOR
J2
24VAC
ST1
21
20
Remote
Temperature
Controller
5.4 Mounting on a Roof Curb (cont'd)
The duct furnace requires a separate gas line; gas connection is 1/2". See gas sup-
ply entrance location in
the illustrations. Refer to Paragraph 9.2.1.2 for gas supply
piping and pressure requirements. The Size 300 duct furnace burner operates only at
high fire. Manifold pressure is 3.5" w.c.; see Paragraph 9.2. The high temperature limit
control functions the same as described in Paragraph 9.2.4.
Field wiring is required. Check the wiring diagram for requirements. Follow the wiring
diagram in
FIGURE 11C to connect the field-supplied wiring.
Option JH30 Duct
Furnace Installation
- REDB Unit Installation Manual RECB Unit Installation Manual RDDC Unit Installation Manual RDCC Unit Installation Manual RDDB Unit Installation Manual RDCB Unit Installation Manual RDC Unit Installation Manual RCC Unit Installation Manual RDB Unit Installation Manual RCB Unit Installation Manual REDC Unit Installation Manual MAPSIV Unit Installation Manual MAPSIII Unit Installation Manual