Form I-MAPSIII&IV, P/N 222917R9, Page 27

3. Discharge Duct Supports - Position the two discharge duct side

supports as shown in

FIGURES 12A and 12D, and attach to cross

supports as shown in STEP 12 in

FIGURE 12B.

4. Return Air Duct Supports - Position the two return air side supports and

the end support as shown in

FIGURES 12A and 12D. Follow STEP 7 in

FIGURE 12B to attach.

5. Check the roof curb for squareness. The curb must be adjusted so that

the diagonal measurements are equal within a tolerance of ± 1/8" (3mm).

6. Level the roof curb. To ensure a good weatherproof seal between the

cabinet curb cap and the roof curb, the curb must be leveled in both

directions with no twist end to end. Shim as required and secure curb to

the roof deck before installing flashing.

7. Install field-supplied flashing. See FIGURE 12C.

8. If the unit has return air and/or down discharge, insert ductwork into the

duct openings. See ductwork sizes in

FIGURE 12E.

9. Before placing the unit on the curb:

If ductwork is being installed from the top, slide the ductwork down into the discharge and return air openings. See

dimensions in

FIGURE 12E. Ductwork should be sized slightly smaller with a minimum 3/4" duct flange that can be

attached on all sides of the duct connection. See the system installation manual for ductwork requirements

Apply 1/4" x 1-1/4" foam sealant tape to both the top surface of the curb rails and the top surface of the perimeter of

the dividers, being sure to make good butt joints at all corners. The sealant tape must be applied to prevent water

leakage into the curb area due to blown rain and capillary action.

Roofing

Felts (by others)

Cant Strip

(by installer)

Counter Flashing

(by installer)

MUST be

sealed

between

curb cap and

roof curb.

2 x 6

Wood

Nailer

Insulation

Weld, bolt, or lag screw

curb to deck structure.

Curb

Cap

Cabinet W

all

Roof Curb

FIGURE 12C - Cross Section

of Roof Curb Installation

IMPORTANT NOTES: Area

enclosed by roof curb must

comply with clearance to

combustible materials. If

the roof is constructed of

combustible materials, area

within the roof curb must be

ventilated, left open, or covered

with non-combustible material

which has an "R" value of at

least 5. If area within curb is left

open, higher radiated sound

levels may result.

Roof Curb Dimensions

and Weight by Model

and Size

FIGURE 12D -

Dimensions - MAP

®

SIII

Cabinet D, Option CJ3

Roof Curb (Curb height

is 16" / 406mm.)

Return

Air Duct Opening

for inserting ductwork with flange down from the roof.

Discharge

Duct

Opening

for inserting

ductwork

with flange

down from

the roof

X - Outside of Curb Rail

Y - Inside of Curb Rail

Top width of mounting rails is 1-5/8” (41mm). Always apply caulking to all mounting surfaces (curb rails, supports,

and duct dividers) before placing unit.

Top View

of Roof Curb

Unit Airflow

5-1/2” (140mm)

1-5/8”

(41mm)

1-5/8”

(41mm)

1-5/8”

(41mm)

1-5/8”

(41mm)

*48”

(1219mm)

*10-1

1/16”

(271mm)

*30-1

1/16”

(779mm)

*Z

*Use these dimensions for assembling the roof curb; follow the instructions on pages 26-27.

DO NOT USE these dimensions for sizing ductwork; see FIGURE 12E on page 28.

2-39/64”

(66mm)

4-3/8” (111mm)

*26-7/16” (672mm)

*72-5/16”

(1837mm)

92-1/4”

(2343mm)

89”

(2261mm)

2-piece cross support (with splice bracket

outside of the duct opening)

2-piece cross support (with splice bracket

outside of the duct opening)

2-piece cross support (with splice bracket)

2-piece cross support (with splice bracket outside of the duct opening)

Cabinet D MAPS

®

III Models

and Cooling Sizes

with Gas Heat

Section

with Electric

Heat Section

Illustration Codes - FIGURE 12D

Approx

Curb Wt

X

Y

Z

Dimensions - inches

lbs

RCB 360, 480, 600, 720

None

None

200-7/16

197-3/16

87-9/16

710

RECB 360, 480, 600, 720

120, 180

200-7/16

197-3/16

87-9/16

710

RDCB 360, 480, 600, 720

500, 600, 700, 800

None

200-7/16

197-3/16

87-9/16

710

1000, 1200, 1400, 1600

232-7/8

229-5/8

120

740

RDB 418, 444, 538, 564, 602, 658,

684, 722, 804, 842

None

None

200-7/16

197-3/16

87-9/16

710

REDB 418, 444, 538, 564, 602, 658,

684, 722, 804, 842

120, 180

200-7/16

197-3/16

87-9/16

710

RDDB 418, 444, 538, 564, 602, 658,

684, 722, 804, 842

500, 600, 700, 800

None

200-7/16

197-3/16

87-9/16

710

1000, 1200, 1400, 1600

232-7/8

229-5/8

120

740

Dimensions - mm

kg

RCB 360, 480, 600, 720

None

None

5091

5009

2224

322

RECB 360, 480, 600, 720

120, 180

5091

5009

2224

322

RDCB 360, 480, 600, 720

500, 600, 700, 800

None

5091

5009

2224

322

1000, 1200, 1400, 1600

5915

5833

3048

322

RDB 418, 444, 538, 564, 602, 658,

684, 722, 804, 842

None

None

5091

5009

2224

322

REDB 418, 444, 538, 564, 602, 658,

684, 722, 804, 842

120, 180

5091

5009

2224

322

RDDB 418, 444, 538, 564, 602, 658,

684, 722, 804, 842

500, 600, 700, 800

None

5091

5009

2224

322

1000, 1200, 1400, 1600

5915

5833

3048

336